Fig. 63: Setting parameters
3. Tap the field (1) behind the required parameter.
4. Enter and confirm parameter.
Enabling and disabling Interval mode.
Fig. 64: Enabling Interval mode.
5. Tap button (1).
ð
Interval mode is enabled. The button has a
green border.
6. Tap button (1).
ð
Interval mode is disabled. The button is
gray.
8.7.4 Alarm data
Process parameter
Overpressure shut off [bar]
Input of a maximum supply pressure. If the
value is exceeded, the pump switches off.
An alarm message appears. Values
between 8 and 21 bar can be parameter-
ized.
Overspeed pressure control [s]
If there is a leakage in the ring pipe system,
the pump is switched off during the produc-
tion operation. Values between 10 and 150 s
can be parameterized. If the time parameter
and the maximum rotational speed of 80 Hz
is exceeded, the pump switches off. An
alarm message appears.
Pressure control lower pressure threshold [bar]
A warning appears if the bottom pressure
threshold is reached. Values between 0 and
17 bar can be parameterized.
Pressure control upper pressure threshold [bar]
A warning appears if the top pressure
threshold is reached. Values between 2 and
19 bar can be parameterized.
Set alarm data.
Personnel:
System operator
1. Open the “Parameter management” menu
using the
button.
2. Switch to “Alarm data” menu using the button
.
Fig. 65: Alarm data
User level 2 required.
1. Tap the field (1) behind the required parameter.
2. Enter and confirm parameter.
8.8
Measured values
Personnel:
System operator
1. Use the button
to open the “Measured
values” menu.
Fig. 66: Measured values (example)
ð
The time range of the display is 30 min.
Visualizer
05/2017
EcoPUC MC - MCU00003EN
34/68