3.2.1  Terminal assignment of the RMZ

3 GND

Connection of external 

detectors with  

terminating resistor

Total 

output 

max. 9.8 W

12 + 24 V
14

1 +

Output 24 V DC 

door-holding device(s)

4 –

2

External manual release 

with terminating resistor (43 kOhm)

10

7 NO

Potential free changeover 

contact low voltage (SELV) 

24 V AC/DC, 1 A

8 NC
9  C

11

Potential-free terminal

16

Bus

3.2.2  The RMZ’s operating status display

Functions of the LEDs

LED on 

    LED off 

Operation indicator LED 1 (green/red)

Operation: green 

 

Smoke detector alarm: red 
 

 

Manual release button alarm: red 

   

   

   

   

Service display LED 2 (yellow) 

Maintenance due: flashing 

   

     

Contamination: flashing 

   

   

   

 

Malfunction: permanent 

 

Malfunction: flashing 

   

 

Incorrect wiring to the ceiling smoke detector/manual 
release button

3.3  Optional components

•  Concealed cable loop for the door closer’s power 

supply via the door leaf, e.g. dormakaba KÜ 480 and 
LK12

•  Additional smoke detector RM-N

3.4  Technical data

3.4.1  Door closer

Supply voltage operating 
voltage
Power consumption

24 V DC +/- 15 % 
approx. 3 W

Ambient temperature:

-15°C to +40°C

Rel. humidity:

up to 93%  
(non condensing)

Protection class:

IP 54

3.4.2  RMZ

Input:

230 V AC +10 %/–15 % 
120 mA/28 VA/50 Hz

Output:

24 V DC/460 mA/11 W

Protection class:

IP 30

Protection category:

II

Smoke switch:

24 V DC/50 mA

Temperature:

-20 °C/+40 °C

Rel. humidity: 

max. 93 % without 
condensation

4  Mounting

The figures in the picture section of this manual show 
the
mounting for DIN-L. For DIN-R, the instructions must 
be mirror-inverted.

4.1  Mounting variants

The TS 97 FLR-K XEA can be mounted DIN-L or DIN-R 
on the hinge side or opposite side to the hinge.

4.2  Mounting the door closer and slide rail

  2 - 9 

Carry out the mounting according to the enclosed 
illustrated instructions.

4.3  Make electrical connections to the 

RMZ

 10 

1. 

Connect the 230 V connection cable. To maintain 
the protection category II   (protective 
insulation), lay the 230-V supply with double 
insulation up to the connection terminal.

2. 

Ensure the strain relief of the mains power supply 
leading to the RMZ. The protective earth must 
not be used electronically. Connect the provided 
protective earth to the support terminal (PE).

3. 

Close the touch protection.

4. 

Screw the touch protection on.

5. 

Connect the cable from the door closer.

7. 

Connect the HT manual release button and the 
optional ceiling smoke detectors to the RMZ 
according to the enclosed wiring diagrams.

4.4  Set DIP switches

 11 

1. 

Set the DIP switches to the appropriate position. 

 

1  OFF  =  automatic reset  

 

 

 

  (delivery state) 

 

 

ON   =  manual reset 

 

 

 

  (A manual reset is required  

 

 

 

  for freewheel door closers) 

 

 

 

  For this type of function, stick the  

 

 

 

  enclosed label on the housing  

     
 

2  OFF  =  1-radial operation (line) 

 

 

ON   =  2-radial operation (star)

 

3  OFF  =  without optional ceiling smoke    

     

 detector 

 

 

ON   =  with optional ceiling smoke detector

Summary of Contents for TS 97 FLR-K XEA

Page 1: ...ms 3 2 4 Requirements for the electrical installation by the customer 3 3 Product description 3 3 1 RMZ 3 3 2 DIP switch on the RMZ 3 3 2 1 Terminal assignment of the RMZ 4 3 2 2 The RMZ s operating status display 4 3 3 Optional components 4 3 4 Technical data 4 3 4 1 Door closer 4 3 4 2 RMZ 4 4 Mounting 4 4 1 Mounting variants 4 4 2 Mounting the door closer and slide rail 4 4 3 Make electrical co...

Page 2: ...y if not averted CAUTION This signal word indicates a situation of potential risk which could lead to minor or slight injury if not averted TIPS AND RECOMMENDATIONS This signal word indicates useful information for efficient and trouble free operation 1 6 Symbols used 1 The picture number in the text document refers to an illustration in the picture section of the mounting instructions 1 2 Step by...

Page 3: ...Connect the 230 V AC power supply to the RMZ A circuit breaker B 10A B 16A must be present in the supply circuit The circuit breaker also serves as a disconnecting device to disconnect the RMZ from the power supply The transverse section of the mains power supply must only be a max 3 x 1 5 mm NYM Connect the cables for the 24 V DC power supply from the RMZ to the TS 97 FLR K XEA door closer The su...

Page 4: ...ke switch 24 V DC 50 mA Temperature 20 C 40 C Rel humidity max 93 without condensation 4 Mounting The figures in the picture section of this manual show the mounting for DIN L For DIN R the instructions must be mirror inverted 4 1 Mounting variants The TS 97 FLR K XEA can be mounted DIN L or DIN R on the hinge side or opposite side to the hinge 4 2 Mounting the door closer and slide rail 2 9 Carry...

Page 5: ...ned and closed manually without resistance from the door closer 4 10 2 RMZ automatic door closing CAUTION Risk of eye and respiratory injury Follow the application and safety instructions on the test gas and the safety data sheet 20 1 Open the door 2 Spray the test gas on the smoke detector according to the manufacturers instructions The operation indicator switches to alarm red The door closes Du...

Page 6: ...the replacement period has been reached 7 Disassembly recycling and disposal Disassembly is carried out in reverse order to the mounting and must be carried out by qualified personnel DANGER Danger to life through electric current Works on electrical units must only be carried out by qualified electricians Before starting work on electrical units and equipment make sure that it is de energized and...

Page 7: ...7 TS 97 FLR K XEA 2019 08 dormakaba Mounting instructions Maintenance WN 059876 45532 ...

Page 8: ...Translation of the original manual subject to change without notice dormakaba Deutschland GmbH DORMA Platz 1 58256 Ennepetal Germany T 49 2333 793 0 F 49 2333 793 4950 www dormakaba com ...

Reviews: