TS 97 FLR-K XEA

2019-08

dormakaba Mounting instructions

About this document

WN 059876 45532

About this document

1.1  Contents and purpose 

This manual describes the installation, startup, 
maintenance and disassembly of the TS 97 FLR-K XEA 
door closer. The manual’s picture section is partly 
supported by text in this section of the manual.

1.2  Target group 

The hold-open system’s mounting, commissioning, 
maintenance and disassembly must only be carried 
out by qualified personnel that have been authorized 
by dormakaba. The acceptance inspection must only 
be carried out by qualified personnel certified for 
this by dormakaba. The operation of the hold-open 
system may be carried out by any person who is 
mentally and physically able of doing so.

1.3  Other applicable documents

The following documents belong to the unit’s 
complete documentation and must be observed: 
•  Drilling template
•  Picture section for mounting instructions
•  RMZ/RM-ED connection diagrams 
•  Information sheet about the use of hold-open 

systems

•  General design approval

1.4  Documents storage 

This manual must be kept during the service life of the 
product and must be passed on with the product. 

1.5  Safety instructions

DANGER

This signal word indicates a situation of 
immediate risk, which will lead to death or 
serious injury if not averted.

CAUTION

This signal word indicates a situation of 
potential risk, which could lead to minor or 
slight injury if not averted.

TIPS AND RECOMMENDATIONS

This signal word indicates useful information 
for efficient and trouble-free operation.

1.6  Symbols used

 1 

The picture number in the text 

document refers to an illustration in 
the picture section of the mounting 
instructions

1.

2.

Step-by-step graphics

1

2

Position numbers of components

The icon indicates the installation 
stages of the supplied cable loop

The icon indicates installation stages if 
the cable loop supplied is not mounted.

1.6.1  Tool icons

Allen wrench,  
e.g. wrench size 3

1.7  Glossary

GS 

Slide rail 

HT 

Manual release button

RM-N  Smoke detector
RMZ   Smoke detector panel
TS  

Door closer

2  Safety

DANGER

Danger to life through electric current

Works on electrical units must only be 
carried out by qualified electricians.
•  Before starting work on electrical units 

and equipment, make sure that it is 
de-energized and that this condition is 
maintained for the duration of the work.

2.1  Intended use

The TS 97 FLR-K XEA is intended solely for the 
controlled closing of swing doors with the following 
properties:
•  Maximum door leaf weight 180 kg
•  Maximum door leaf weight 1,400 kg
•  Maximum door opening angle when mounting the 

door closer on the hinge side approx. 145°. 

•  Maximum door opening angle when mounting 

the door closer on the opposite side to the hinge 
approx. 105°.

The door opening angle must be limited by a 
doorstop.

Summary of Contents for TS 97 FLR-K XEA

Page 1: ...ms 3 2 4 Requirements for the electrical installation by the customer 3 3 Product description 3 3 1 RMZ 3 3 2 DIP switch on the RMZ 3 3 2 1 Terminal assignment of the RMZ 4 3 2 2 The RMZ s operating status display 4 3 3 Optional components 4 3 4 Technical data 4 3 4 1 Door closer 4 3 4 2 RMZ 4 4 Mounting 4 4 1 Mounting variants 4 4 2 Mounting the door closer and slide rail 4 4 3 Make electrical co...

Page 2: ...y if not averted CAUTION This signal word indicates a situation of potential risk which could lead to minor or slight injury if not averted TIPS AND RECOMMENDATIONS This signal word indicates useful information for efficient and trouble free operation 1 6 Symbols used 1 The picture number in the text document refers to an illustration in the picture section of the mounting instructions 1 2 Step by...

Page 3: ...Connect the 230 V AC power supply to the RMZ A circuit breaker B 10A B 16A must be present in the supply circuit The circuit breaker also serves as a disconnecting device to disconnect the RMZ from the power supply The transverse section of the mains power supply must only be a max 3 x 1 5 mm NYM Connect the cables for the 24 V DC power supply from the RMZ to the TS 97 FLR K XEA door closer The su...

Page 4: ...ke switch 24 V DC 50 mA Temperature 20 C 40 C Rel humidity max 93 without condensation 4 Mounting The figures in the picture section of this manual show the mounting for DIN L For DIN R the instructions must be mirror inverted 4 1 Mounting variants The TS 97 FLR K XEA can be mounted DIN L or DIN R on the hinge side or opposite side to the hinge 4 2 Mounting the door closer and slide rail 2 9 Carry...

Page 5: ...ned and closed manually without resistance from the door closer 4 10 2 RMZ automatic door closing CAUTION Risk of eye and respiratory injury Follow the application and safety instructions on the test gas and the safety data sheet 20 1 Open the door 2 Spray the test gas on the smoke detector according to the manufacturers instructions The operation indicator switches to alarm red The door closes Du...

Page 6: ...the replacement period has been reached 7 Disassembly recycling and disposal Disassembly is carried out in reverse order to the mounting and must be carried out by qualified personnel DANGER Danger to life through electric current Works on electrical units must only be carried out by qualified electricians Before starting work on electrical units and equipment make sure that it is de energized and...

Page 7: ...7 TS 97 FLR K XEA 2019 08 dormakaba Mounting instructions Maintenance WN 059876 45532 ...

Page 8: ...Translation of the original manual subject to change without notice dormakaba Deutschland GmbH DORMA Platz 1 58256 Ennepetal Germany T 49 2333 793 0 F 49 2333 793 4950 www dormakaba com ...

Reviews: