SafeRoute® System
2019-03
WN 059722 45532
dormakaba
Commissioning
System manual
If the illuminated ring does not change to the
operation indicator (permanently lit red):
1.
Use the key switch to push right to left.
‣ The illuminated ring on the emergency button
lights up red permanently.
‣ The STVxxx locks.
→
The SCU-UP/SCU-TL is configured.
If the alarm signal "The emergency button is pressed"
is pending (see Chap. 7 on page 8), reset the
alarm signal:
1.
Turn and hold the key to the right on the key
switch.
2.
Press the emergency button for 1 s and then
release.
3.
Push the key over the middle to the left and bring
it back to the middle position.
4.
Remove the key.
‣ The electric locking device is active.
→
The SCU-UP/SCU-TL is configured.
5.1.2 SCU-DR as SafeRoute® Control Unit
(from Basic license)
The status display during the configuration takes
place via LEDs on the board. The LEDs light up or
flash depending on the status of the connected
DCW® component.
In 1 In 2 In 3 In 4
BTR
DCW
CPU2
CPU1
SLI
Out2
Out1
Out 3 Out 4
Fig. 3
Arrangement of the LEDs on the SCU-DR board
5.1.2.1 Configure an SCU-DR
1.
Connect the power supply.
‣ The DCW® LED lights up red when correctly
connected.
‣ The SLI LED lights up yellow when the license
is inserted.
‣ The LEDs from In 1 to In 4 change to the
initialization view and display the license.
In 1 - 4 off
no/defective license card
In 4 on
SLI Basic
In 3 on
SLI Standard
‣ The illuminated ring on the emergency button
flashes briefly and changes to the rainbow
view.
2.
Press and hold the S4 service button on the SCU-
DR for 12 s.
‣ After 12 s, the illuminated ring on the
emergency button lights up blue.
‣ The BTR LED flashes green.
‣ The connected components are detected and
displayed on the illuminated ring (flashing
green/blue alternately).
3.
Press and hold the S4 service button for 3 s.
‣ The BTR LED lights up green.
‣ The DCW® LED lights up red.
‣ The CPU1 and CPU2 LEDs light up red (CPU1)
and yellow (CPU2).
‣ The illuminated ring on the emergency button
lights up red permanently.
4.
Use the key switch to push right to left.
‣ The illuminated ring on the emergency button
lights up red permanently.
‣ The STVxxx locks.
→
The SCU-DR is configured.
5.2 Parameterization with TMS Soft®
(from Basic license)
With TMS Soft® and the SafeRoute® configuration
software, the functions of the components and
the SafeRoute® system can be adapted. For more
information, see the TMS Soft® handbook.
The settings made with the SafeRoute® configuration
software must be entered in the respective door unit’s
inspection log.
5.3 Handover of the documentation to the
facility operator
All documents relevant for proper operation are
handed over to the facility operator after initial
commissioning:
• The installed individual components’ assembly
instructions and documents
• The operation manual
• The door unit’s inspection log
• This system manual