background image

Quantum II RFID ECU 

 

PK3724_T   05-19 

7

5  Wiring the ECU

Power Leads 
The ECU requires 12-24 volts AC or DC input. Two White (Non-Polarized) wire leads are provided for supplying 

power to the reader. Ensure that voltage going to the ECU does not exceed 24 volts. Power supplies must be in 

a separate enclosure and rated properly.  Refer to your local Electrical and Building Codes.

Relay Leads 
The ECU is equipped with a 5 Amp Dry Contact Relay that can be configured either Normally Open (NO) or 

Normally Closed (NC). 

CAUTION

WARNING

IMPORTANT

Observe all local electrical and building codes

Red relay lead = Common (COM) contact

Blue relay lead = Normally Open (NO) contact

Black relay lead = Normally Closed (NC) contact

Wire the appropriate contact (COM and either NO or NC) to the elevator call buttons. Refer to fig 10 for typical 

wiring configuration.

Chassis ground Lead 
The Green lead on the ECU is used for chassis ground. Connect the Green lead between one of the spade ter-

minals on the ECU PCB and one of the reader mounting screws. Refer to fig 9.

Reader connections

Reader Ribbon

Insert the reader ribbon into the ribbon connector on the ECU PCB. Observe proper orientation. The gold 

contacts of the connector should mate with the gold contacts on the reader ribbon. Refer to fig 8 for proper 

orientation

Reader Power

Plug the reader power Red lead into the white power port on the ECU PCB. Refer to fig 9. 

Summary of Contents for Quantum II RFID ECU

Page 1: ...Quantum II RFID ECU Installation instructions PK3724 T 2019 05 EN ...

Page 2: ...1 A21710 COLOR Quantum II RFID Reader Assembly 1 2 A32760 COLOR Quantum II RCU Faceplate 1 3 94640 RCU Gasket 1 4 A22770 Mounting Bracket 1 5 A28732 RMO PCB Assembly RFID MT2 1 6 A37010 Sleeve Quantum II RCU 3 7 A37000 Washer Flat 8 Screw 1 8 73400 014 Screw 8 32 1 2 PH Philips 3 9 A27490 Tie Wrap 14 RCU 1 10 55250 Nut Wire 4 11 A28360 Wire Harness RCU PCB 1 12 50170 COLOR Screw 6 32 x 1 FH 4 ...

Page 3: ...Contact Relay that can be configured either Normally Open NO or Normally Closed NC The relay is rated for five Amps at 250VAC or 5 AMPS at 30VDC Typically the NO set of contacts are used so that the ECU will work like the elevator call button to complete the circuit to call the elevator to the specific floor CAUTION WARNING IMPORTANT Review your local Fire Electrical and Building Codes before inst...

Page 4: ...ation 1 Disassemble the reader from the 4 X 4 mount ing plate Refer to the exploded diagram Figure 1 2 Retain all of the mounting hardware brackets and ECU PCB for re use 3 Insert the reader through the elevator panel cut out Flush mount prep and re assemble the PCB mounting bracket onto the back side of the eleva tor panel using the mounting hardware 4 Re install the ECU PCB onto the bracket usin...

Page 5: ... 5 3 38 2 30 1 20 2 05 54 1 71 2 37 ELEVATOR PANEL 3X Ø 281 20 1 75 87 1 50 50 30 TOP C L Ø 88 4 Installation Steps Flush Mount Reader Figure 4 Flush Mount Reader Installation Dimensions Figure 5 Flush Mount Reader Installation Template ...

Page 6: ... 2 05 1 71 2 37 3 25 1 63 1 81 91 2 25 3 25 4X 6 32 TAPPED HOLE C L C L 4 56 4 48 ELEVATOR PANEL 4 Installation Steps Surface Mount Reader Figure 6 Surface Mount Reader Installation Dimensions Figure 7 Surface Mount Reader Installation Template ...

Page 7: ...d Common COM contact Blue relay lead Normally Open NO contact Black relay lead Normally Closed NC contact Wire the appropriate contact COM and either NO or NC to the elevator call buttons Refer to fig 10 for typical wiring configuration Chassis ground Lead The Green lead on the ECU is used for chassis ground Connect the Green lead between one of the spade ter minals on the ECU PCB and one of the r...

Page 8: ... bolt input Leave INTACT Orange Loop Cut for 1 second relay cycle Relay 5 Amp SPDT Reader power connector Relay leads Red Common COM Blue Normally Open NO Black Normally Closed NC Power leads 12 to 24 volts MAX AC or DC 125mA Fuse Saflok PN A28450 1 Amp Green pilot lamp ON when power is applied Chassis Ground Reader ribbon Gold Contacts Figure 9 ECU PCB ...

Page 9: ...CU PK3724_T 05 19 9 5 Wiring the ECU Figure 10 Typical ECU Wiring Floor call Button Common Floor call Button Floor call Button Floor call Button White White Blue NO Red COM Black NC 12 to 24 Volts AC or DC Not Supplied ...

Page 10: ...Manual for programming instructions Present the appropriate key construction or property to the face of the reader The reader should flash the green LED and activate the relay for 5 seconds During the 5 seconds press the appropriate call button on the elevator panel If the ECU is programmed to the property verify that all property programmed keys function to the specifica tions of the properties k...

Page 11: ...ogramming in the System Manual Relay not activating Bad relay lead connections Verify relay lead connections See diagram X Bad ECU relay Verify relay contacts with a meter Replace PCB if defective 2019 dormakaba All trademarks and registered trademarks are the property of their respective owners Model Quantum II RFID ECU FCC and IC Warnings This device complies with part 15 of the FCC Rules Operat...

Page 12: ...rmakaba com dormakaba Customer services support 1 800 999 6213 1 248 837 3700 General information www dormakaba us Online consumable orders www saflokstore com To access all of our easy steps please visit our support website www dormakabalodgingsupport com ...

Reviews: