DORMA
TS 99 FLR-K EN 2-5
Terminal assignment FLR-K
Connect manual pushbutton and any required ceiling-
mounted detectors – see connection diagrams.
Terminal resistors must be properly installed!
Insert and connect RS smoke alarm module (option).
The alarm module cannot be used if relay contacts
7, 8 and 9 are already in use.
In order to comply with protection class II (total
insulation), the 230V power cable should be installed
with double insulation up to the connection terminal.
Remove cable insulation at the end.
Connect power cable to terminals .
Close the shock hazard protection cover
and screw
down .
Reset
Status display flashes green as soon as there is no
longer any smoke or test gas in the smoke chamber.
Reset is performed by pressing the reset pushbutton.
Attach the enclosed RESET label.
Remove the red protective cap from the smoke
detector unit.
Switch on power supply – status display flashes green .
Press the RESET pushbutton
– status display
should show green.
Setting the free-swing function
Set the switch in the junction box to “ON”
(24V DC for hold-open device) .
Open the door leaf to the required hold-open position .
The closer spindle is held in this position by the
electro-hydraulic hold-open device, but the door can
be freely moved thanks to the free-swing arm
assembly.
Leave the door open.
Functional test of manual pushbutton
Interrupt power supply using manual pushbutton (e.g.
DORMA HT) . The hold-open device is de-energised
and the door is closed .
Status display flashes green.
Press the RESET pushbutton . – status display
should show green.
Clip on end caps .
Break out the tab as marked for the recess in the
cover .
Clip on cover .
15
16
17
18
19
20
Functional checks
Ensure compliance with the instructions for use and
also the safety instructions provided on the test gas
container and safety datasheet.
Open door leaf .
Spray test gas (Hekatron 918/5) from a distance of
approx. 10-15cm towards the smoke chamber .
After approx. 4-6 short bursts, the status display
should switch to alarm (red). If the FLR-K is equipped
with the RS smoke alarm module (option), an audible
alarm is also sounded.
The hold-open device is tripped and released, and the
door closes .
Status display flashes green as soon as there is no
longer any smoke or test gas in the smoke chamber.
Reset is performed by pressing the RESET pushbutton .
Status display should show green.
Fit dust protection cover supplied so that dust is
prevented from entering the smoke detector during
any subsequent building or finishing work.
Prior to final commissioning, remove the dust
protection cover and perform a further function
check in accordance with step 22.
Function of the LEDs
LED on
LED off
Status display LED 1 (green/red)
Standby: green
Alarm: red
Manual reset necessary: green flashing
(see also item 17)
Service display LED 2 (yellow)
Servicing due: flashes
Contamination: flashes
Fault: continuous
FINAL INSPECTION AND MAINTENANCE
Instruction sheet relating to the use and application
of hold-open systems.
3)
If the FLR-K lintel-mounted smoke detector is used in
rooms with a high dust content, ensure compliance
with the specified maintenance intervals. These may
even have to be reduced in order to ensure that dust
deposits in the detector do not give rise to nuisance
tripping.
EN 14600 Appendix C
FURTHER INFORMATION / REGULATIONS
Approval certificate
Instruction sheet relating to the use and application
of hold-open systems.
3)
Guidelines for hold-open systems published by the
Institute for Building Technology, Berlin
3)
, or
equivalent national guidelines
22
23
24
☞
☞
DORMA GmbH + Co.KG
DORMA Platz 1 D-58256 Ennepetal • Tel. +49 (0) 23 33 / 793-0 • www.dorma.com
Door Control Division
Postfach 40 09 D-58247 Ennepetal • Fax +49 (0) 23 33 / 79 34 95
☞
☞
☞
3)
These documents are only printed in German as they refer
exclusively to the German market.
Subject to change without notice