DORMA

TS 99 FLR-K EN 2-5

Terminal assignment FLR-K

Connect manual pushbutton and any required ceiling-

mounted detectors – see connection diagrams.

Terminal resistors must be properly installed!

Insert and connect RS smoke alarm module (option).

The alarm module cannot be used if relay contacts

7, 8 and 9 are already in use.

In order to comply with protection class II     (total

insulation), the 230V power cable should be installed

with double insulation up to the connection terminal.

Remove cable insulation at the end.

Connect power cable to terminals  .

Close the shock hazard protection cover 

 

and screw

down  .

Reset

Status display flashes green as soon as there is no

longer any smoke or test gas in the smoke chamber.

Reset is performed by pressing the reset pushbutton.

Attach the enclosed RESET label.

Remove the red protective cap from the smoke

detector unit.

Switch on power supply – status display flashes green  .

Press the RESET pushbutton 

 

– status display

should show green.

Setting the free-swing function

Set the switch in the junction box to “ON”

(24V DC for hold-open device)  .

Open the door leaf to the required hold-open position  .

The closer spindle is held in this position by the

electro-hydraulic hold-open device, but the door can

be freely moved thanks to the free-swing arm

assembly.

Leave the door open.

Functional test of manual pushbutton

Interrupt power supply using manual pushbutton (e.g.

DORMA HT)  . The hold-open device is de-energised

and the door is closed  .

Status display flashes green.

Press the RESET pushbutton  . – status display

should show green.

Clip on end caps  .

Break out the tab as marked for the recess in the

cover  .

Clip on cover  .

15

16

17

18

19

20

Functional checks

Ensure compliance with the instructions for use and
also the safety instructions provided on the test gas
container and safety datasheet.

Open door leaf  .

Spray test gas (Hekatron 918/5) from a distance of

approx. 10-15cm towards the smoke chamber  .

After approx. 4-6 short bursts, the status display

should switch to alarm (red). If the FLR-K is equipped

with the RS smoke alarm module (option), an audible

alarm is also sounded.

The hold-open device is tripped and released, and the

door closes  .

Status display flashes green as soon as there is no

longer any smoke or test gas in the smoke chamber.

Reset is performed by pressing the RESET pushbutton  .

Status display should show green.

Fit dust protection cover supplied so that dust is

prevented from entering the smoke detector during

any subsequent building or finishing work.

Prior to final commissioning, remove the dust
protection cover and perform a further function
check in accordance with step 22.

Function of the LEDs

LED on

LED off

Status display LED 1 (green/red)

Standby: green

Alarm: red

Manual reset necessary: green flashing

(see also item 17)

Service display LED 2 (yellow)

Servicing due: flashes

Contamination: flashes

Fault: continuous

FINAL INSPECTION AND MAINTENANCE

Instruction sheet relating to the use and application

of hold-open systems.

3)

If the FLR-K lintel-mounted smoke detector is used in
rooms with a high dust content, ensure compliance
with the specified maintenance intervals. These may
even have to be reduced in order to ensure that dust
deposits in the detector do not give rise to nuisance
tripping.

EN 14600 Appendix C

FURTHER INFORMATION / REGULATIONS

Approval certificate

Instruction sheet relating to the use and application

of hold-open systems.

3)

Guidelines for hold-open systems published by the

Institute for Building Technology, Berlin 

3)

, or

equivalent national guidelines

22

23

24

DORMA GmbH + Co.KG

DORMA Platz 1 D-58256 Ennepetal • Tel. +49 (0) 23 33 / 793-0 • www.dorma.com

Door Control Division

Postfach 40 09 D-58247 Ennepetal • Fax +49 (0) 23 33 / 79 34 95

3)

These documents are only printed in German as they refer

     exclusively to the German market.

Subject to change without notice

Summary of Contents for TS 99 FLR-K

Page 1: ...aten TS 99 FLR K Eingang 230 V AC 10 15 120 mA 28 VA 50 Hz Ausgang 24 V DC 460 mA 11 W Schutzart IP 30 Schutzklasse II Rauchschalter 24 V DC 50 mA Temperatur 20 C 60 C Technische Daten EMF Betriebsspannung 24 V DC Leistungsaufnahme 2 W Einschaltdauer 100 ED Arbeiten an Elektroanlagen dürfen nur von geschulten Fachkräften ausgeführt werden Überprüfen ob die bauseitige Stromzuführung 230 VAC spannun...

Page 2: ...tung erfolgt über den Reset Taster Betriebs anzeige leuchtet grün Endkappenblenden aufclipsen Markierte Aussparung an der Verkleidung ausbrechen Verkleidungen aufclipsen 15 16 17 18 19 20 21 Änderungen vorbehalten Funktionsprüfung Anwendungs und Sicherheitshinweise auf dem Prüfgas und Sicherheitsdatenblatt beachten Türflügel öffnen Prüfgas Hekatron 918 5 aus ca 10 15 cm Entfernung in Richtung Rauc...

Page 3: ...otection IP 30 Protection class II Smoke switch 24 V DC 50 mA Temperature 20 C 60 C Technical Data Hold open Device EMF Operating voltage 24 V DC Power input 2 W Duty factor 100 continuous duty Work on electrical equipment and systems may only be performed by properly trained specialist personnel Check to ensure that the line power supply 230V AC has been disconnected and is no longer live IA 10 A...

Page 4: ...heet Open door leaf Spray test gas Hekatron 918 5 from a distance of approx 10 15cm towards the smoke chamber After approx 4 6 short bursts the status display should switch to alarm red If the FLR K is equipped with the RS smoke alarm module option an audible alarm is also sounded The hold open device is tripped and released and the door closes Status display flashes green as soon as there is no l...

Reviews: