Section 2 - Control Cabinet Installation 

 

Installation of the 2348-010 elevator control board(s) and cabinet(s) should be coordinated with the 
elevator service company.  The cabinets should be installed in close proximity to the elevator 
electronic control panel so that wiring between the elevator electronic control panel and the 2348-010 
board(s) is simplified.  110 VAC power must be available nearby to power the transformer(s) that will 
supply 16 VAC power to the 2348-010 board(s).  One 16 VAC power transformer is required for each 
elevator car (shaft) controlled. 

 

1.  Open the cabinet and remove any ribbon cables from the 2348-010 board (systems with 

two or more boards only). 

2.  Remove the four screws from each corner of the board and then remove the board from 

the cabinet.  

CAUTION: Touch a proper ground with your hands before removing 

the board(s) from the cabinet

.  This will discharge any static electricity and prevent 

electrostatic discharge damage to the board. 

3.  Mount the cabinets.  Each cabinet has four mounting holes located in the corners.  Be 

sure that the mounting screws do not protrude into the cabinet in such a way that they 
can cause a short to the back of the 2348-010 board. 

4.  Make any conduit connections at this time.  

5.  Clean out the cabinet being sure that any metal shavings are removed from the cabinet. 

6.  Re-install the 2348-010 board(s) and the ribbon cables. 

 

 

 

 

Summary of Contents for 2348

Page 1: ...2348 Elevator Control Boards DoorKing Inc 120 Glasgow Avenue Inglewood California 90301 U S A Phone 310 645 0023 Fax 310 641 1586 www doorking com P N 2348 065 REV D 12 07 Copyright 2001 DoorKing Inc...

Page 2: ...Page 2 2348 065 D 12 07...

Page 3: ...King Inc to notify any persons of any such revisions or changes Additionally DoorKing Inc makes no representations or warranties with respect to this manual This manual is copyrighted all rights reser...

Page 4: ...Page 4 2348 065 D 12 07...

Page 5: ...ion 16 3 2 3 Relay Settings 17 3 2 4 Lobby Hall Up Call Relay 17 3 3 Switch Settings Description 18 Section 4 Wiring Information 4 1 General Information 19 4 2 Control Board Terminal Identification 20...

Page 6: ...Page 6 2348 065 D 12 07...

Page 7: ...ator car electrical umbilical cable The elevator control system is able to restrict elevator button operation by interrupting the button wiring between the elevator car and the elevator control electr...

Page 8: ...by hall call feature is desirable in that the timer for the floor button does not become active until the elevator reaches the lobby or ground floor For example if the timer was set in the software to...

Page 9: ...dant on the revision level of the 1830 series telephone entry access controller circuit board not the 2348 elevator control board Refer to the table below Controller Circuit Board Revision Level Time...

Page 10: ...17 32 2 4 6 8 10 12 14 16 33 48 3 6 9 12 15 18 21 24 49 64 4 8 12 16 20 24 28 32 Table 2 The 2348 010 boards are housed in either a small 1816 102 or large 1816 100 cabinet The small cabinet will hol...

Page 11: ...binet and remove any ribbon cables from the 2348 010 board systems with two or more boards only 2 Remove the four screws from each corner of the board and then remove the board from the cabinet CAUTIO...

Page 12: ...D CA 90301 Title Date Rev Dwg No 4 0 35 25 2 0 4 625 12 2 5 875 DIA 2 PL FOUR BOARD ENCLOSURE Quad Enclosure for 2348 010 Board P N 2348 081 A 10 03 M2348 065 2 2 0 12 375 1 625 4 125 35 10 25 875 875...

Page 13: ...OD CA 90301 Title Date Rev Dwg No TWO BOARD ENCLOSURE Dual Enclosure for 2348 010 Board P N 2348 080 A 10 03 M2348 065 3 2 5 2 0 12 375 2 0 4 625 12 875 DIA 2 PL 1 625 21 25 10 25 875 875 675 4 125 21...

Page 14: ...Page 14 2348 065 D 12 07...

Page 15: ...ccess system 1833 1835 1837 1838 can have up to eight 8 MASTER 2348 010 boards connected to it with each master controlling an additional three 3 boards Therefore the access system can accommodate up...

Page 16: ...tor terminals and receives weigand data from the access control system There can only be one MASTER board per shaft If there is more than one MASTER board in the system two or more elevator shafts it...

Page 17: ...t to operate as either a normally open N O or normally closed N C device The normal setting for the LOBBY HALL CALL relay is N O If SW 2 switch 8 is in the ON position the LOBBY HALL CALL relay WILL N...

Page 18: ...ormation SW 2 BOTTOM SWITCH SWITCH FUNCTION SETTING DESCRIPTION 1 2 Floor Identification Identifies which floors the elevator board is controlling See table 4 page 16 3 thru 7 Spare OFF Spare switches...

Page 19: ...ickup therefore it is preferable that you keep power wire runs as short as possible The 2348 010 elevator control board contains a number of static sensitive components that can be damaged or destroye...

Page 20: ...Terminals 1 18 Terminals 19 36 Terminals 37 54 Terminals 55 72 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 Title Date Rev Dwg No 11 03 M2348 065 5 A 2348 010 Control Board DOORKING INC INGLEWOOD CA 90301 Relay Sh...

Page 21: ...ct Input 54 Relay 8 19 Not Used 55 20 Data 1 Wiegand Input 1 56 Relay 7 21 Data 0 Wiegand Input 1 57 22 Common Wiegand Input 1 58 Relay 6 23 Data 1 Wiegand Input 2 59 24 Data 0 Wiegand Input 2 60 Rela...

Page 22: ...nclosure that can house up to four 4 transformers to meet your power requirements Cabinet 1 Shaft 1 Cabinet 2 Shaft 2 Cabinet 3 Shaft 3 Cabinet 4 Shaft 4 Cabinet 5 Shaft 5 Cabinet 6 Shaft 6 Cabinet 7...

Page 23: ...tor service technician only We recommend that all functions of the elevator control board be tested prior to wiring the floor control relays to the elevator electronic control panel For safety reasons...

Page 24: ...garding this switch input Connect a Normally Open N O ground floor detect switch to terminals 17 and 18 fig 7 Note Dry contact no voltage The switch must activate when the elevator car is at the lobby...

Page 25: ...plied Ribbon Cable between boards 8 Floor relays are rated for 5 amp 125 Volt 7 7 8 8 2348 010 Board 1 Relays 1 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 3...

Page 26: ...ator Control Panel 2348 010 Access Controller Elevator Car Elevator Shaft 1 2 3 8 2 Common Floor Control Floor Control Floor Control Floor Control Floor Control Floor Control Floor Control Floor Contr...

Page 27: ...all floor control relays and LED s will be off when the board is powered up When a floor level access command is initiated the relay and LED will activate providing a contact closure which enables the...

Page 28: ...l for building tenants For 24 hour access to floors you must program a security level for 24 hr 7 day access and click on all used floor locations Select Relay and Floor s Within the Security Level yo...

Page 29: ...ay address at the relay elevator screen System Information Security Level Relay Elevator Relay Elevator screen This addresses which system relay is inside each elevator car This tells the system that...

Page 30: ...PROVIDE ELEVATOR CONTROL FUNCTIONS This security level provides 24 7 access at all reader locations However elevator commands will not be sent from the phone system to elevator board Security Level 0...

Page 31: ...e restrictions will apply This does not affect visitor elevator control Security Level 02 time zone 2 Programmed for access 7 AM 9 PM M F Relays To program elevator control select the relays that refe...

Page 32: ...oor Level access for the resident Remember Security Level 01 will not provide elevator control FL Residents Floor This identifies which floor the resident lives on Visitors granted access by the resid...

Page 33: ...l panel the Lobby Hall Up Call feature cannot be used The elevator reference number also identifies which elevators will respond to the floor button control for visitor access and how long the residen...

Page 34: ...Page 34 2348 065 D 12 07...

Page 35: ...ng three 3 boards controlling the elevator car in the shaft are powered from the MASTER elevator control board Be sure that all ribbon cables connecting the boards together are plugged in properly Che...

Page 36: ...lays operating will repeat 10 times and then automatically quit and will take about four 4 minutes The purpose of this test is to confirm that communication exists between the access control system bo...

Page 37: ...guidelines in Table 5 1st Number 2nd Number 3rd Number 4th Number The shaft number that the wire pertains to The board number that the wire pertains to Terminal number that the wire connects to The f...

Page 38: ...37 16 16 38 38 39 39 15 15 40 40 41 41 14 14 42 42 43 43 3 13 44 44 45 45 12 12 46 46 47 47 11 11 48 48 49 49 10 10 50 50 51 51 9 9 52 52 53 53 8 8 54 54 55 55 7 7 56 56 57 57 6 6 58 58 59 59 5 5 60...

Page 39: ...16 16 38 38 39 39 15 15 40 40 41 41 14 14 42 42 43 43 3 13 44 44 45 45 12 12 46 46 47 47 11 11 48 48 49 49 10 10 50 50 51 51 9 9 52 52 53 53 8 8 54 54 55 55 7 7 56 56 57 57 6 6 58 58 59 59 5 5 60 60 6...

Page 40: ...inals Floor No Wire ID 37 37 16 38 16 38 39 39 15 40 15 40 41 41 14 42 14 42 43 43 3 44 13 44 45 45 12 46 12 46 47 47 11 48 11 48 49 49 10 50 10 50 51 51 9 52 9 52 53 53 8 54 8 54 55 55 7 56 7 56 57 5...

Page 41: ...16 16 38 38 39 39 15 15 40 40 41 41 14 14 42 42 43 43 3 13 44 44 45 45 12 12 46 46 47 47 11 11 48 48 49 49 10 10 50 50 51 51 9 9 52 52 53 53 8 8 54 54 55 55 7 7 56 56 57 57 6 6 58 58 59 59 5 5 60 60 6...

Page 42: ...37 16 16 38 38 39 39 15 15 40 40 41 41 14 14 42 42 43 43 3 13 44 44 45 45 12 12 46 46 47 47 11 11 48 48 49 49 10 10 50 50 51 51 9 9 52 52 53 53 8 8 54 54 55 55 7 7 56 56 57 57 6 6 58 58 59 59 5 5 60...

Page 43: ...16 16 38 38 39 39 15 15 40 40 41 41 14 14 42 42 43 43 3 13 44 44 45 45 12 12 46 46 47 47 11 11 48 48 49 49 10 10 50 50 51 51 9 9 52 52 53 53 8 8 54 54 55 55 7 7 56 56 57 57 6 6 58 58 59 59 5 5 60 60 6...

Page 44: ...37 16 16 38 38 39 39 15 15 40 40 41 41 14 14 42 42 43 43 3 13 44 44 45 45 12 12 46 46 47 47 11 11 48 48 49 49 10 10 50 50 51 51 9 9 52 52 53 53 8 8 54 54 55 55 7 7 56 56 57 57 6 6 58 58 59 59 5 5 60...

Page 45: ...16 16 38 38 39 39 15 15 40 40 41 41 14 14 42 42 43 43 3 13 44 44 45 45 12 12 46 46 47 47 11 11 48 48 49 49 10 10 50 50 51 51 9 9 52 52 53 53 8 8 54 54 55 55 7 7 56 56 57 57 6 6 58 58 59 59 5 5 60 60 6...

Page 46: ...37 16 16 38 38 39 39 15 15 40 40 41 41 14 14 42 42 43 43 3 13 44 44 45 45 12 12 46 46 47 47 11 11 48 48 49 49 10 10 50 50 51 51 9 9 52 52 53 53 8 8 54 54 55 55 7 7 56 56 57 57 6 6 58 58 59 59 5 5 60...

Page 47: ...16 16 38 38 39 39 15 15 40 40 41 41 14 14 42 42 43 43 3 13 44 44 45 45 12 12 46 46 47 47 11 11 48 48 49 49 10 10 50 50 51 51 9 9 52 52 53 53 8 8 54 54 55 55 7 7 56 56 57 57 6 6 58 58 59 59 5 5 60 60 6...

Page 48: ...inals Floor No Wire ID 37 37 16 38 16 38 39 39 15 40 15 40 41 41 14 42 14 42 43 43 3 44 13 44 45 45 12 46 12 46 47 47 11 48 11 48 49 49 10 50 10 50 51 51 9 52 9 52 53 53 8 54 8 54 55 55 7 56 7 56 57 5...

Page 49: ...16 16 38 38 39 39 15 15 40 40 41 41 14 14 42 42 43 43 3 13 44 44 45 45 12 12 46 46 47 47 11 11 48 48 49 49 10 10 50 50 51 51 9 9 52 52 53 53 8 8 54 54 55 55 7 7 56 56 57 57 6 6 58 58 59 59 5 5 60 60 6...

Page 50: ...37 16 16 38 38 39 39 15 15 40 40 41 41 14 14 42 42 43 43 3 13 44 44 45 45 12 12 46 46 47 47 11 11 48 48 49 49 10 10 50 50 51 51 9 9 52 52 53 53 8 8 54 54 55 55 7 7 56 56 57 57 6 6 58 58 59 59 5 5 60...

Page 51: ...16 16 38 38 39 39 15 15 40 40 41 41 14 14 42 42 43 43 3 13 44 44 45 45 12 12 46 46 47 47 11 11 48 48 49 49 10 10 50 50 51 51 9 9 52 52 53 53 8 8 54 54 55 55 7 7 56 56 57 57 6 6 58 58 59 59 5 5 60 60 6...

Page 52: ...37 16 16 38 38 39 39 15 15 40 40 41 41 14 14 42 42 43 43 3 13 44 44 45 45 12 12 46 46 47 47 11 11 48 48 49 49 10 10 50 50 51 51 9 9 52 52 53 53 8 8 54 54 55 55 7 7 56 56 57 57 6 6 58 58 59 59 5 5 60...

Page 53: ...16 16 38 38 39 39 15 15 40 40 41 41 14 14 42 42 43 43 3 13 44 44 45 45 12 12 46 46 47 47 11 11 48 48 49 49 10 10 50 50 51 51 9 9 52 52 53 53 8 8 54 54 55 55 7 7 56 56 57 57 6 6 58 58 59 59 5 5 60 60 6...

Reviews: