MAINTENANCE  

To keep the boiler/hot water tank unit in perfect working order, both appliances should by inspected 
yearly by 

DOMUSA TEKNIK

 authorised technicians. In particular, the following are recommended: 

- The inside of the hot water tank should be thoroughly cleaned once a year. The primary circuit 

should be drained first, before draining the hot water tank. 
- If the hot water tank includes electronic cathode protection, this should be inspected once a year 

to ensure it is functioning correctly. 

- The pressure of the primary installation must be kept between 0.1 and 0.15 MPa (1 and 1.5 bar). 
- Make sure the safety valve and the drain valve are working correctly. 
- If the installation has been out of use for a long time, check the hot water tank feed pump is 

working correctly. To do this, remove the front cover from the pump, leaving the pump shaft 

visible. If the shaft does not turn, disconnect the pump using the pump switch. Gently press the 

shaft down with a suitably sized screwdriver and turn it in both directions. Then connect the 

switch again. 

It is recommended for the user to periodically check the pressure and temperature levels of the hot 

water tank and the state of the valves, connections and accessories. 

8

 

START-UP  

For the 

guarantee to be valid

, the hot water tank must be started up by an 

Official DOMUSA TEKNIK 

Technical Assistance Service

. Before starting it up, the following must be ensured: 

- The electrical connection of the hot water tank is correctly made. 
- The installation is filled with water and the draining has been done correctly. 
- The drain valve is working properly. 
- The primary flow and return connections and the hot and cold water connections have been 

correctly made. 

- The thermostat has been properly adjusted and the electric cabling complies with regulations. 
- There are no leaks from the splices and connections. 

9

 

DELIVERY OF THE INSTALLATION  

After the initial start-up of the appliance, the Technical Assistance Service will explain to the user how 

the hot water tank works, making any observations they consider relevant. 

It is the responsibility of the installer to explain to the user the functioning of any control devices 

belonging to the installation and not supplied with the hot water tank. 

Summary of Contents for SANIT 1000

Page 1: ...INSTALLATION AND OPERATING INSTRUCTIONS SANIT 300 SANIT 500 SANIT 750 SANIT 1000 SANIT 1000 SBH ER 0170 1996 CGM 04 392 ...

Page 2: ...e given to the user Read the warnings and recommendations in the manual carefully as they contain important information on the safety use and maintenance of the installation These hot water tanks are to be installed by skilled personnel only in accordance with the legislation in force and following the manufacturer s instructions The start up of these hot water tanks and any maintenance operations...

Page 3: ...ES 12 4 5 5 DHW SAFETY VALVE 12 5 OPERATION 13 6 DIAGRAM AND ELECTRICAL CONNECTION 13 6 1 ELECTRICAL DIAGRAM 13 6 2 ELECTRICAL CONNECTION TO THE BOILER 14 6 3 DIAGRAMS FOR CONNECTION TO DOMUSA TEKNIK BOILERS 14 6 4 INSTRUCTIONS FOR ELECTRICAL CONNECTION OF THE SANIT STORAGE HEATER TO THE FOLLOWING BOILERS 14 7 MAINTENANCE 16 8 START UP 16 9 DELIVERY OF THE INSTALLATION 16 10 DRAINING THE TANK 17 1...

Page 4: ...e Cleaning and user maintenance shall not be made by children without supervision The electrical main power supply connection must respect the current legislation making possible a complete disconnection of the tank in order to make any maintenance operation safely Look Diagram and electrical connection chapter 1 1 Frost precautions When there is danger of frost and particularly in areas with very...

Page 5: ...ANIT 300 SS EP V SP 2 1 3 ES TR R 1 Front cover 2 Bridge cover 3 Control panel SP Primary outlet EP Primary inlet ES Domestic cold water inlet SS Domestic hot water outlet TR Resistance socket R Recirculation intake V Drainage ...

Page 6: ... SS EP V SP 1 2 3 R TR ES 1 Front cover 2 Bridge cover 3 Control panel SP Primary outlet EP Primary inlet ES Domestic cold water inlet SS Domestic hot water outlet TR Resistance socket R Recirculation intake V Drainage ...

Page 7: ...2 3 TR ES SS R EP SP V 1 Front cover 2 Bridge cover 3 Control panel SP Primary outlet EP Primary inlet ES Domestic cold water inlet SS Domestic hot water outlet TR Resistance socket R Recirculation intake V Drainage ...

Page 8: ...EP SP V SS TR R ES 1 Front cover 2 Bridge cover 3 Control panel 4 Lateral cover SP Primary outlet EP Primary inlet ES Domestic cold water inlet SS Domestic hot water outlet TR Resistance socket R Recirculation intake V Drainage ...

Page 9: ... 2 1 3 EP V SP SS TR R ES 1 Front cover 2 Bridge cover 3 Control panel SP Primary outlet EP Primary inlet ES Domestic cold water inlet SS Domestic hot water outlet TR Resistance socket R Recirculation intake V Drainage ...

Page 10: ...ntrol is for adjusting the desired temperature of the hot water stored in the tank 2 Element switch This is for starting up and stopping the optional back up element of the hot water tank 3 Thermometer This indicates the temperature of the hot water stored in the tank ...

Page 11: ...ng boilers 4 1 Connection The diagram below shows an example of the installation of Sanit hot water tanks with a heating boiler 4 2 Equipment 1 Feed pump 2 Non return valve 3 Automatic drain valve 4 Dielectric sleeve 5 0 7 MPa 7 bar safety valve 6 Non return valve 7 Shut off valve 8 Stainless steel hot water tank 9 Polyurethane insulation 10 Resistance socket ...

Page 12: ... no higher than the design pressure To prevent heat loss through the hot water pipes in accumulation systems an anti thermal siphon must be installed at the hot water tank outlet The hot water pipe must be insulated at least up to the anti thermal siphon A copper return circuit should not be used When the chlorine concentration in the Domestic Water exceeds 250 mg dm3 it is recommended that anti c...

Page 13: ...of storage heaters To install it carefully read the assembly instructions supplied with the cathodic protection Figura 1 4 5 2 Electrical element All Sanit hot water tanks have a socket for connecting an electrical element DOMUSA TEKNIK optionally supplies three elements of 1 5 2 5 and 3 5 kW To install them carefully read the assembly instructions supplied with the elements Figura 2 4 5 3 18L DHW...

Page 14: ...de of stainless steel To install the dielectric sleeves carefully read the assembly instructions supplied with them Figura 4 4 5 5 DHW safety valve All Sanit hot water tanks are designed to work at a maximum DHW pressure of 0 7 MPa 7 bar To prevent this pressure from being exceeded DOMUSA TEKNIK recommends fitting a safety valve to the DHW circuit calibrated to a maximum of 0 7 MPa 7 bar The safet...

Page 15: ...TRICAL CONNECTION The Sanit range of hot water tanks is especially designed for easy electrical connection to a wide range of heating boilers The special design of its electrical connections enables the boiler hot water tank unit to provide heating and domestic hot water with automatic functioning incorporating a hot water priority function to the joint operation of the two appliances When install...

Page 16: ...ical diagram for each model of boiler see the boiler instructions manual To connect the TDHW tube first remove the bridges from the boiler connector block and then connect the TDHW tube as shown in the figures below depending on the boiler model 6 3 Diagrams for connection to DOMUSA TEKNIK boilers 11 1 2 3 B lack B lue B rown TDHW tube for connection to boiler SIR ENA C AL FD 13 14 15 B lack B lue...

Page 17: ...m Remove the thermostat bulb from the bulb holder on the storage heater and insert the temperature sensor bulb in its place Connect the storage heater feed pump to the boiler supply connector block J2 terminals 6 and 7 see the Connection Diagram For a correct hydraulic installation carefully follow the assembly and connection instructions supplied with the storage heater 1 3 5 6 7 8 9 10 11 4 J 1 ...

Page 18: ...irections Then connect the switch again It is recommended for the user to periodically check the pressure and temperature levels of the hot water tank and the state of the valves connections and accessories 8 START UP For the guarantee to be valid the hot water tank must be started up by an Official DOMUSA TEKNIK Technical Assistance Service Before starting it up the following must be ensured The ...

Page 19: ... to the drain socket on the botton of the tank Check the hose is correctly connected to the tank drain socket Run the hose to a nearby floor drain This must be at a lower level than the tank Begin the suction process so that the water begins to flow and wait until it drains completely SANIT 300 500 750 1000 ...

Page 20: ...lisher 2 CFER000082 tapered plug 3 GELESAN008 Electrical board 4 CFER000086 1 black embellisher 5 SCON000090 Elliptical plug 6 Bridge 7 M8 washer 8 M8 nut Pos Code Name 9 CACU000038 Bridge cover 10 CFOL000037 Brass plug 11 MVAR010027 Seal 12 CFER000008 1 red plug 13 CFER000083 Seal 14 CFER000087 1 black embellisher 15 CFOL000020 1 chromed plug ...

Page 21: ...ug 3 GELESAN008 Electrical board 4 SCON000090 Elliptical plug 5 MVAR010027 Seal 6 Bridge 7 M8 washer 8 M8 nut Pos Código Denominación 9 CACU000038 Tapa puente 10 CFER000008 1 red plug 11 CFER000083 Seal 12 CFER000087 1 black embellisher 13 CFOL000020 1 chromed plug 14 CFER000085 black embellisher 15 CFER000082 tapered plug 16 CFOL000037 Brass plug ...

Page 22: ...lug 3 GELESAN008 Electrical board 4 CFER000085 black embellisher 5 CFER000082 tapered plug 6 CFER000087 1 black embellisher 7 CFER000080 1 red plug 8 SCON000430 Elliptical plug 9 CFOL000020 1 chromed plug Pos Código Denominación 10 Bridge 11 M8 washer 12 M8 nut 13 CACU000038 Cover bridge 14 CFOL000037 Brass plug 15 MVAR010027 Seal 16 CFER000083 Press tow ...

Page 23: ...Seal 5 M8 washer 6 CFER000060 M8 Nut cover 7 M8 nut 8 CACU000038 Cover bridge 9 Bridge 10 CFOL000037 Brass plug 11 Lateral cover Pos Código Denominación 12 CFER000080 1 red plug 13 CFER000087 1 black embellisher 14 CFOL000020 1 chromed plug 15 CFER000083 Seal 16 CFER000082 tapered plug 17 GELESAN008 Electrical board 18 CFER000085 black embellisher 19 M12 Screw 20 Lateral joint 21 Lateral inox cove...

Page 24: ...R000085 black embellisher 4 SCON000090 Elliptical plug 5 M8 washer 6 CFER000060 M8 Nut cover 7 M8 nut 8 CACU000038 Cover bridge 9 Bridge 10 CFOL000037 Brass plug Pos Código Denominación 11 MVAR010027 Seal 12 CFER000080 1 red plug 13 CFER000087 1 black embellisher 14 CFOL000020 1 chromed plug 15 CFER000083 Seal 16 CFER000082 tapered plug 17 GELESAN008 Electrical board ...

Page 25: ...2 1 3 6 7 5 Pos Code Name 1 CELC000099 Knob 2 CELC000007 Control thermostat 3 CACU000036 Control panel cover 4 CACU000037 Control panel plug Pos Code Name 5 CACU000035 Control panel 6 CELC000136 Thermometer 7 CELC000025 Switch ...

Page 26: ...Sanit 24 12 DIAGRAMS AND MEASUREMENTS SS TR ES R SP EP SP EP R SS ES TR SANIT 300 SANIT 500 SANIT 750 SANIT 1000 TR ES SS R EP SP ...

Page 27: ...427 1427 G mm 483 H mm 184 255 Base measurement mm 608 758 858 1058 1058 Height measurement mm 1758 1798 1941 1768 1768 Recirculation intake R 3 4 H 3 4 H 3 4 H 3 4 H 3 4 H Cold water inlet ES 1 M 1 M 1 1 2 M 1 1 2 M 1 1 2 M Hot water outlet SS 1 M 1 M 1 1 2 M 1 1 2 M 1 1 2 M Primary inlet outlet EP SP 3 4 H 1 H 1 M 1 M 1 M Resistance intake TR 1 1 4 H 1 1 4 H 1 1 4 H 1 1 4 H 1 1 4 H Drainage V M ...

Page 28: ...3 3 Empty weight Kg 74 120 166 240 240 Full weight Kg 374 620 916 1240 1240 Functioning Qp 1m3 h 1077 1370 2213 2582 2582 Qp 3m3 h 1117 1537 2481 2896 2896 Continuous flow l h 30º Qp 5m3 h 1168 1582 2555 2981 2981 Qp 1m3 h 680 1061 1619 2096 2096 Qp 3m3 h 686 1089 1664 2149 2149 Peak flow l 10min 30º Qp 5m3 h 695 1097 1679 2163 2163 Qp 1m3 h 1577 2203 3463 4248 4248 Qp 3m3 h 1617 2370 3731 4562 45...

Page 29: ...tion are to be carried out by personnel authorised by DOMUSA TEKNIK 4 The commercial guarantee will be null and void in the following cases If the annual inspection by DOMUSA TEKNIK authorised personnel has not been carried out If the boiler has not been installed in accordance with the applicable laws and regulations concerning this type of appliance If the boiler has not been started up immediat...

Page 30: ...Sanit 28 NOTES ...

Page 31: ...29 NOTES ...

Page 32: ... Bº San Esteban s n Ellesmere Port CH65 9BF 20737 ERREZIL Gipuzkoa Tel 0151 909 6222 Tel 34 943 813 899 www domusateknik com DOMUSA TEKNIK reserves the right to make modifications of any kind to its product characteristics without prior notice CDOC000222 CDOC000222 07 16 ...

Reviews: