background image

KRA Refrigeration System Installation, Operation & Maintenance Manual

 

L-3571 ENGLISH

13

4.

The best way to make sure the unit is charged properly is by the subcooling method. This will ensure that you have a 
good liquid seal to the TXV with no flash gas or vapor. Typical subcooling is 6 to 10°F/-14 to -12°C depending on the 
condensing temperatures. Refer to Figure 10: Refrigerant Pressure-Temperature Chart, page 21.

A

DJUSTING

 

THE

 TXV

On rare occasions, 

a qualified technician may need to make an adjustment,

 but these adjustments are slight. Use a wrench 

to remove the nut covering the superheat adjustment valve stem. This exposes the valve stem. Once the system has had 
sufficient running time to stabilize the box temperatures, adjustment should be made in 1/4-turn increments only. Use the 
wrench to make adjustments. After each incremental adjustment, allow 15 to 20 minutes for the expansion valve diaphragm to 
stabilize. 

Looking at the stem-end of the valve:

Turn the valve stem clockwise to close the valve; this will decrease the flow of refrigerant and increase the superheat. 

Turn the valve stem counter-clockwise to open the valve; this will increase the flow of refrigerant and decrease the 
superheat.

One full turn of the valve stem equals 4.5° of superheat. 

Follow directions with the valve. Replace the outer nut, and tighten to 3 ft-lbs. Insulate valve and bulb fully.

TXV M

ETERING

 D

EVICE

If service or replacement is needed, follow manufacturer’s recommendations for more information. Call Dometic Technical 
Support. 

S

IGHT

 G

LASS

See “Sight Glass/Moisture Indicator” on page 9“ in the “Installing the Refrigeration System” section.

USER MAINTENANCE

S

EAWATER

 S

YSTEM

Check the seawater strainer daily. Remove any debris. If you are in waters where jellyfish or other debris are a problem, you 
may find it necessary to add a strainer on the outside of the through-hull fitting.

Verify that all seawater connections are tight, and check for water flow from the overboard discharge. The centrifugal seawater 
pump does not need any regular maintenance.

D

EFROSTING

Defrosting of your freezer box is required to keep the unit working at peak performance. Defrost the unit whenever more than 
1/4" (7 mm) of ice or frost has accumulated on the plates or box sides. 

To defrost, remove all the contents from the box and remove drain plug (if applicable), then disconnect the power to the KRA 
unit. Leave unit off until all ice has melted. Be sure to replace drain plug once unit has finished defrosting (if applicable).

To accelerate the defrost process, remove plug and use fresh water to melt ice and rinse the box clean. Never use a mechanical 
device to remove ice. Damage to box liner is not covered under Dometic Warranty.

W

INTERIZING

 

THE

 S

YSTEM

Make sure all water has drained from the refrigerated box. On seawater-cooled units, close the seacock, and remove inlet hose 
from pump and outlet hose from unit to allow all water to drain from the system. Drain and clean seawater strainer. 

NOTE

Check ability of vacuum pump to achieve 200-400 microns by connecting micron gauge directly to pump. If it does not 
achieve 200-400, service or replace pump.

NOTE

If moisture has been a problem, refer to Refrigeration Bulletin 02-1 for instructions on clean up. This bulletin is 
available on the Marine Resource Center under Technical Field Notices: “Control of Moisture in Refrigeration 
Systems” (FN#175-I2).

CAUTION

System contains R-404A refrigerant. Recovery machines containing mineral-based oils should not be used.

Summary of Contents for KRA 433X 1161

Page 1: ...ery precaution has been taken in the preparation of this manual to ensure its accuracy However Dometic assumes no responsibility for errors and omission Neither is any liability assumed for damages re...

Page 2: ...Condensing Unit 10 THERMOSTAT OPERATION 10 Operating the Dometic Control 10 Parameter Programming 11 Modbus Addresses for Dometic STIIC Interface 12 SERVICING YOUR REFRIGERATION SYSTEM 12 REFRIGERANT...

Page 3: ...s NEC in the U S CEC in Canada 3 Open the electrical disconnect switch es before electrically connecting the unit 4 Before operating the unit be certain it is properly grounded 5 The units contain ref...

Page 4: ...refrigerant expansion valve externally equalized expansion valve thermostat and seawater system for water cooled titanium condensers WARNING To avoid possible explosion death or injury practice safe h...

Page 5: ...s not constant 4 10 cm of R7 insulation is required It is best to use as much insulation as is practical Call the Dometic Applications Department for advice on larger sized boxes or if you are unsure...

Page 6: ...eded for the installation UNPACKING AND INSPECTION Units are securely packed in shipping containers approved by the International Safe Transit Association Upon arrival carefully check all items agains...

Page 7: ...ce then add the minimum free area to get the minimum free area total for all of the units This also applies to the space airflow For example if a KRA 433X and a KRA 450X unit are in an enclosed space...

Page 8: ...ould be in good thermal contact with the refrigerant tubing Attach it to the closest straight piece of tubing exiting the last box If either the expansion valve or its sensing bulb is located outside...

Page 9: ...ons will extend the compressor s run time significantly resulting in shortened unit life To set the thermostat see Thermostat Operation on page 10 Thermostat bulb or thermistor should be mounted one t...

Page 10: ...n off the first box turn on the other one Wait approximately 10 minutes Turn all boxes on and check for frost on box plate surfaces If not fully frosted check subcool 3 Follow procedures for Starting...

Page 11: ...UP or DOWN buttons to change it then press the SET button to temporarily save it and display the the parameter code again 6 Repeat steps 4 and 5 to set other parameters if needed 7 TO PERMANENTLY SAV...

Page 12: ...t temperature This will expedite the recovery of the refrigerant but is not necessary EVACUATE REFRIGERANT 1 Connect manifold gauges to both high and low side ports Attach center line of gauge set to...

Page 13: ...NANCE SEAWATER SYSTEM Check the seawater strainer daily Remove any debris If you are in waters where jellyfish or other debris are a problem you may find it necessary to add a strainer on the outside...

Page 14: ...y See technician for service 3 Low refrigerant charge Check for a refrigerant leak and repair Evacuate system and recharge with the correct amount of R 404A 4 TXV Mechanical failure Have technician co...

Page 15: ...temperature introduce cooler air into compartment that houses the condensing unit High water temperature while you cannot remedy this problem you can help by introducing cooler air into the compartme...

Page 16: ...S Figure 1 KRA Cabinet Type Condensing Units Figure 2 Various Flat Plate Evaporators Figure 3 Wrapped Box Evaporator Figure 4 Flat Plate Evaporator Designs Figure 5 Digital Thermostat Dometic Control...

Page 17: ...TION PROPRIETARY NOTE THE INFORMATION CONTAINED WITHIN THIS DOCUMENT IS THE PROPERTY OF DOMETIC CORPORATION ANY ATTEMPT TO COPY OR DISTRIBUTE WITHOUT WRITTEN CONSENT FROM DOMETIC CORPORATION SHALL BE...

Page 18: ...ory Insulated REV DATE APR DWG REVISION DESCRIPTION PROPRIETARY NOTE THE INFORMATION CONTAINED WITHIN THIS DOCUMENT IS THE PROPERTY OF DOMETIC CORPORATION ANY ATTEMPT TO COPY OR DISTRIBUTE WITHOUT WRI...

Page 19: ...N DOMETIC APR BY DWG BY SCALE DATE REV DWG PART NUMBER PROPRIETARY NOTE THE INFORMATION CONTAINED WITHIN THIS DOCUMENT IS THE PROPERTY OF DOMETIC CORPORATION ANY ATTEMPT TO COPY OR DISTRIBUTE WITHOUT...

Page 20: ...REV DWG PART NUMBER PROPRIETARY NOTE THE INFORMATION CONTAINED WITHIN THIS DOCUMENT IS THE PROPERTY OF DOMETIC CORPORATION ANY ATTEMPT TO COPY OR DISTRIBUTE WITHOUT WRITTEN CONSENT FROM DOMETIC CORPO...

Page 21: ...KRA Refrigeration System Installation Operation Maintenance Manual L 3571 ENGLISH 21 Figure 10 Refrigerant Pressure Temperature Chart...

Page 22: ...22 L 3571 ENGLISH Figure 11 Wiring Diagram for KRA 433X Unit with 1 Box...

Page 23: ...KRA Refrigeration System Installation Operation Maintenance Manual L 3571 ENGLISH 23 Figure 12 Wiring Diagram for KRA 433X Unit with 2 Boxes...

Page 24: ...RPORATION SHALL BE CONSIDERED UNLAWFUL AND CAN BE CONTESTED IN A COURT OF LAW PART NUMBER DWG REV DATE SCALE DWG BY APR BY DOMETIC REVISION DESCRIPTION DWG APR DATE REV 339501 C 339501 KRA 450X KRA 1...

Page 25: ...KRA Refrigeration System Installation Operation Maintenance Manual L 3571 ENGLISH 25 Figure 14 Wiring Diagram for KRA 450X Unit with 3 Boxes...

Page 26: ...26 L 3571 ENGLISH NOTES...

Page 27: ...KRA Refrigeration System Installation Operation Maintenance Manual L 3571 ENGLISH 27 NOTES...

Page 28: ...rineSales dometic com 24 7 TECH SUPPORT FOR UNITED STATES AND CANADA 8 00 AM to 5 00 PM Eastern Time 1 800 542 2477 After hours and weekends 1 888 440 4494 INTERNATIONAL SALES AND SERVICE Europe and t...

Reviews: