CoolAir SP950
Using the parking cooler
17
7.5
Extracting condensation (SP950 with SP950T roof
evaporator unit only)
The condensated water which accumulates due to the way the system works is auto-
matically extracted at intervals during operation.
You can pump out the condensated water manually when necessary:
I
➤
Switch off the system.
➤
Press and hold the
and
–
buttons simultaneously.
➤
In addition, press the
button briefly.
✓
The firmware version appears in the digital display for 5 seconds.
✓
000
then appears in the digital display and the system starts the extraction
process for 15 seconds.
You can now let go of the
and
–
buttons.
✓
The compressor and the fan do not switch on.
✓
The system switches off automatically.
I
If you want to tilt the driver’s cab, you first need to drain the condensation manually.
➤
Keep repeating this procedure until the pump starts making a clearly audible,
loud noise while draining.
✓
There is then no more condensation left in the system.
➤
Press the
button until the pump switches off.
A
NOTE
Before winter, extract the condensed water from the system to avoid
damage caused by freezing water.
NOTE
To stop the extraction early press the
button until the pump switches
off.
NOTICE!
Avoid prolonged dry periods as this can damage the pump (indicated
by loud noise while draining).