Assembling the device
62
Installation of the mounting frame on a switch box
Proceed as follows if you use a
switch box:
Guide the connection cables
through the mounting frame.
Attach the mounting frame to the
switch box.
Screw the mounting frame
directly onto the switch box with
four screws (4 x 12).
Connecting the Access Manager (control unit) of the ENiQ Module
Reader/Module Reader Terminal
ATTENTION!
Destruction of the input assemblies due to voltage and
current peaks caused by feedback effects
Make sure that the maximum voltage sustaining capacity
and current carrying capacity are not exceeded during joint
operation of the device with an inductive load e. g. E-
opener.
Use separate voltage supplies if necessary.
ATTENTION!
Damage to the contact pins on the device.
Only tighten the screws of the connecting terminals when
they are not inserted on the device.
ATTENTION!
Functional problem through damage to the radio antenna.
Make sure that the exposed radio antenna on the device
does not become bent or damaged in any other way.
Make sure that the values stated below for electric strength and current
carrying capacity of the inputs and outputs are not exceeded.
ENiQ Module Reader control unit, potential-free switch/button, control unit inputs
Max. cable resistance
<10 Ω
Max. cable length
<20 m