DOLD VARIMETER RCM IL 5882 Installation / Monitoring Technique Download Page 1

1

10.11.16 en / 789

Your advantages

•  Preventive fire and system protection
•  Increasing the availability of plants by early fault detection
•  As option with external or internal residual current transformer
•  Protection against manipulation by sealable transparent cover 
  over setting switches

Features

•  According to IEC/EN 62 020
•  for AC and pulsating DC currants Type A to IEC/TR 60755
•  9 tripping values from 10 mA to 10 A or from 10 mA ... 30 A
•  Frequency range 20 ... 2000 Hz
•  Selection of manual or automatic reset
•  With prewarning
•  With test and reset button
•  Broken wire detection
•  Short reaction time
•  With adjustable delay t

v

•  De-energized on trip
•  LED indication for auxiliary supply and state of contact
•  2 x 1 changeover contact
•  Devices available in 3 enclosure versions:
  IL 5882:  63 mm deep with terminals near to the bottom to be  

 

   

 

mounted in consumer units or industrial distribution  

 

   

 

systems according to DIN 43 880

   

 

- width 35 mm

  

  -

 

for connection of external residual current transformer, 

   

 

  e. g. DOLD ND 5016, ND5019

  SL 5882:  100 mm deep with terminals near to the top to be mounted  

 

   

 

in cabinets with mounting plate and cable ducts

   

 

- width 35 mm

  

  -

 

for connection of external residual current transformer, 

   

 

  e. g. DOLD ND 5016, ND5019

  IR 5882: 

63 mm deep with terminals near to the bottom to be  

 

   

 

mounted in consumer units or industrial distribution  

 

   

 

systems according to DIN 43 88

   

 

-  width 105 mm

   

 

-  with internal residual current transformer

0239971

Detection of insulation faults in grounded voltage systems. The residual 
current relay is used to maintain electrical plants before faults occur. 
Decrease in insulation can be detected and indicated early without inter-
ruption of operation.

IR 5882
with internal 
residual current transformer

ND 5016/024

IL 5882

ND 5016/035

ND 5016/070

Installation / Monitoring Technique

VARIMETER RCM

Residual Current Monitor
IL 5882, SL 5882, IR 5882

Approvals and Markings

Application

Function Diagram

M8368_a

A1/A2

t

Alarm
Prewarning

i

Alarm

Prewarning

11-12

21-22

Test

Reset

manual reset with link X1/X2

with manual reset

11-14

21-24

11-14

tv

tv

tv

manual reset

manual reset

tv

A025518

All technical data in this list relate to the state at the moment of edition. We reserve the right for 
technical improvements and changes at any time.