16
UF 6925 / 30.08.17 en / 895
Circuit Diagrams
Notes
Connection Terminals
Terminal designation
Signal designation
A1+
+
A2
-
S12, S22, S34
Control inputs
S11, S21, S33
Control outputs
13, 14, 23, 24, 33,34
Forcibly guided NO contacts for
release circuit
31, 32
Forcibly guided indicator output
S11
A2
A1
+
M11315
13
K1
K2
23
14 24
33
34
S22
S21
S12
S34
S33
13
34
33
23
14
24
S11
A2
A1
+
M11314
13
K1
K2
23
14 24
31
32
S22
S21
S12
S34
S33
13
32
31
23
14
24
UF 6925.03
UF 6925.22
Setting Cross fault detection
Switch S1 is for selecting with or without cross fault detection at the e-stop
button resp. on safety gate.
For connection please see application examples.
!
ATTENTION! The setting of S1 has to be made before
starting the device.
Setting Start-Mode
S2 is used to change between automatic and manual restart. On automatic
start also the terminals S33 - S34 have to be linked.
With the function manual start a start button has to be connected to
terminals S33-S34. The unit starts up with the negative edge of the start
button signal.
For connection please see application examples.
!
ATTENTION! The setting of S2 has to be made before
starting the device.
Line fault detection on On-button
A line fault detection is only active when S12 and S22 are switched simulta-
neously. If The On-button is closed before S12, S22 is connected to voltage
(also when line fault across On-Button), the output contacts will not close. A
line fault across the On-button which occurred after activation of the relay, will
be detected with the next activation and the output contacts will not close.
!
ATTENTION! If a line fault is removed while the unit is
powered up, the unit switches on.