Configurable Safety System SAFEMASTER PRO
65
0265525 / 16.05.19 en / 101A
UG 6916.12/080
INPUT / OUTPUT MODULE UG 6916.12/080
MEANING
LED
REMED
Y
RU
N
IN
F
AIL
EXT
F
AIL
SEL
IN1÷8
OSSD1÷4
ST
A
TUS1÷4
GREEN
RED
RED
ORANGE
YEL-
L
OW
RED / GREEN
YELLO
W
Inter
nal f
ault
OFF
Flashing
2 or
3 times
OFF
Sho
ws the
ph
ysical
address of
the unit
OFF
RED
OFF
• Retur
n the unit to DOLD
to be repaired
Compatibility error
OFF
Flashing
5 times
OFF
Flashing
5 times
Flashing
5 times
Flashing
5 times
• Fir
mw
are v
ersion not compatib
le with
control unit, retur
n to DOLD
f
or FW upg
rade
OSSD output error
OFF
Flashing
4 times
OFF
OFF
Flashing
4 times
(only the LED corres-
ponding to the output in
FAIL mode)
OFF
• Chec
k the OSSD1/2 connections
• If the prob
lem persists retur
n the
UG 6916.12/080
to DOLD to be repaired
Error in comm
unication
with control unit
OFF
Flashing
5 times
OFF
OFF
OFF
OFF
• Restar
t the system
• If the prob
lem persists retur
n the
UG 6916.12/080
to DOLD to be repaired
Error on other unit
OFF
ON
OFF
OFF
OFF
OFF
• Restar
t the system
• Chec
k which unit is in F
AIL mode
Same type of e
xpansion
unit with same address
detected
OFF
Flashing
5 times
Flashing
5 times
OFF
OFF
OFF
• Change the unit's address
(see NODE SEL)
Ov
er
load on OSSD or load
connected to 24
V DC
ON
OFF
ON
INTPUT
-
Status
Flashes RED
(only the LED corres-
ponding to the output in
FAIL mode )
OUTPUT
-
Status
• V
er
ify OSSD connections
Shor
t circuit or
ov
er
load detected
on status output
ON
OFF
ON
INTPUT
-
Status
OUTPUT
-
Status
Flashing
• V
er
ify output status connections
T
roub
leshooting