General Data
Response time UG 6911.10
This response times depends on the following
Parameterss:
1)
Number of slave modules installed
2)
Number of operators
3)
Number of OSSD outputs
For the right response time refer to the one
calculated by the SAFEMASTER PRO DESIGNER
software (Project report)
UG 6911.10
10,6 ms ÷ 12,6 ms
+ TFilter_Input
UG 6911.10 + 1 Slave
11,8 ms ÷ 26,5 ms
+ TFilter_Input
UG 6911.10 + 2 Slaves
12,8 ms ÷ 28,7 ms
+ TFilter_Input
UG 6911.10 + 3 Slaves
13,9 ms ÷30,8 ms
+ TFilter_Input
UG 6911.10 + 4 Slaves
15 ms ÷ 33 ms
+ TFilter_Input
UG 6911.10 + 5 Slaves
16 ms ÷ 35 ms
+ TFilter_Input
UG 6911.10 + 6 Slaves
17 ms ÷ 37,3 ms
+ TFilter_Input
UG 6911.10 + 7 Slaves
18,2 ms ÷ 39,5 ms
+ TFilter_Input
UG 6911.10 + 8 Slaves
19,3 ms ÷ 41,7 ms
+ TFilter_Input
UG 6911.10 + 9 Slaves
20,4 ms ÷ 43,8 ms
+ TFilter_Input
UG 6911.10 + 10 Slaves
21,5 ms ÷ 46 ms
+ TFilter_Input
UG 6911.10 + 11 Slaves
22,5 ms ÷ 48,1 ms
+ TFilter_Input
UG 6911.10 + 12 Slaves
23,6 ms ÷ 50,3 ms
+ TFilter_Input
UG 6911.10 + 13 Slaves
24,7 ms ÷ 52,5 ms
+ TFilter_Input
UG 6911.10 + 14 Slaves
25,8 ms ÷ 54,6 ms
+ TFilter_Input
Response time UG 6911.12/080
This response times depends on the following
Parameterss:
1)
Number of slave modules installed
2)
Number of operators
3)
Number of OSSD outputs
For the right response time refer to the one
calculated by the SAFEMASTER PRO DESIGNER
software (Project report)
UG 6911.12/080
12,75 ms ÷ 14,75 ms
+ TFilter_Input
UG 6911.12/080 + 1 Slave
13,83 ms ÷ 37,84 ms
+ TFilter_Input
UG 6911.12/080 + 2 Slaves
14,91 ms ÷ 40,00 ms
+ TFilter_Input
UG 6911.12/080 + 3 Slaves
15,99 ms ÷ 42,16 ms
+ TFilter_Input
UG 6911.12/080 + 4 Slaves
17,07 ms ÷ 44,32 ms
+ TFilter_Input
UG 6911.12/080 + 5 Slaves
18,15 ms ÷ 46,48 ms
+ TFilter_Input
UG 6911.12/080 + 6 Slaves
19,23 ms ÷ 48,64 ms
+ TFilter_Input
UG 6911.12/080 + 7 Slaves
20,31 ms ÷ 50,80 ms
+ TFilter_Input
UG 6911.12/080 + 8 Slaves
21,39 ms ÷ 52,96 ms
+ TFilter_Input
UG 6911.12/080 + 9 Slaves
22,47 ms ÷ 55,12 ms
+ TFilter_Input
UG 6911.12/080+ 10 Slaves
23,55 ms ÷ 57,28 ms
+ TFilter_Input
UG 6911.12/080+ 11 Slaves
24,63 ms ÷ 59,44 ms
+ TFilter_Input
UG 6911.12/080+ 12 Slaves
25,71 ms ÷ 61,60 ms
+ TFilter_Input
UG 6911.12/080+ 13 Slaves
26,79 ms ÷ 63,76 ms
+ TFilter_Input
UG 6911.12/080+ 14 Slaves
27,87 ms ÷ 65,92 ms
+ TFilter_Input
Unit connection UG 6911.10, UG 6911.12/080
proprietary 5-pole DOLD IN-RAIL-BUS
Plug in terminal blocks with screw terminals
Max. cross section for connection:
1 x 0,25 ... 2,5 mm
2
solid or
stranded ferruled (isolated) or
2 x 0,25 ... 1 mm
2
solid or
stranded ferruled (isolated)
Insulation of wires or sleeve length:
7 mm
Wire fixing
Captive slotted screw M3
Fixing torque:
0,5 ... 0,6 Nm
Max length of connections:
100 m
Operating temperature:
-10 ÷ 55 °C
Storage temperature:
-20 ÷ 85 °C
Relative humidity:
10 % ÷ 95 %
Altitude:
2,000 m
UL-Data:
The safety functions were not evaluated by UL.
Listing is accomplished according to requirements of Standard UL 508,
“general use applications”
UL-Notes:
For use in Pollution degree 2,
overvoltage category II environment only
Max. ambient temperatur:
55 °C
Wire connection:
60 °C / 75 °C copper conductors onl
AWG 30 ÷ 12 (solid / stranded) Torque 5-7 lb-in
TFilter_Input = max filtering time from among those set on project inputs
(see "INPUT OBJECTS" section").