Configurable Safety System SAFEMASTER PRO
34
0265525 / 16.05.19 en / 101A
OSSD (Output module UG 6912.04/100)
The UG6912.04/100 provides 4 High Current Safety Outputs (2A max per channel).
Two different output configurations (configurable with SAFEMASTER PRO Designer Software) can be set:
• Four single channels (1 Safety Output per channel with its relative feedback input).
• Two dual channels (2 Safety Output per channel with their relative feedback input).
Different output configurations (configurable with SAFEMASTER PRO DESIGNER software)
• 4 single channels (1 Safety Output per channel with its relative feedback input)..
• 2 dual channels (2 Safety Outputs per channel with their relative feedback input).
• 1 dual channel and 2 single channels
Dual Channel OSSD
Configuration with 2 dual channel outputs
(safety category SIL3 / PL e)
Single Channel OSSD
Configuration with 4 single channel outputs
(safety category SIL3 / PL e)
Using UG 6912.04/100 modules with current output >500mA, separate them from adjacent modules by at
least one housing width.
Using single channels OSSD, to maintain Safety Integrity Level (SIL) "3" requirements the OSSD outputs
must be independent.
Common cause failures between OSSD outputs must be excluded by observing an appropriate cable
installation (i.e. separate cable paths).