Function

Function

Failure monitoring

The UG 6946 includes a number of facilities to to detect failures that could 
influence the safety function of the module. The failure check is carried out 
on power up of the unit and in cycles during normal operation. If a failure 
occurs the output relays switch off. The failure state is indicated with the 
LEDs „ERR“ and „UH“.
With safety relevant failures the unit differentiates between external failu-
res (broken wire / offset, simultaneity failure, feedback circuit failure) and 
internal failures.
Broken wire / offset failures and feedback circuit failures can be stored 
or automatic reset after removing the fault. (see chapter failure storing).

Broken wire / offset

The connection wires between UG 6946 and motor are continuously 
monitored for broken wire and on a DC-voltage offset higher then U

an

In the case of a broken wire or offset failure the output relays 
are switched off immediately and the LED „OUT“ lights yellow. 
In addition a failure signal comes up with delay (on broken wire after 2 s 
on offset failure after 8 s): the LED „ERR“ flashes with failure code 2 or 3  
depending on the failure located either between L1-L2 or L1-L3.

Simultaneity of the measuring signals

As additional safety feature the 2 input signals (L2 and L3) are compared 
continuously. This allows to detect also internal failures in one measuring 
channel.

If the signals are different for at least 2.5 s (one channel >U

an

 the other <U

an

simultaneity failure is detected. LED „ERR“ flashes with failure code 5.

If the measured signals return to the same level <U

an

 the error remains 

stored and the outputs are disabled.

The simultaneity failure is only reset when both channels return to > U

an

If after that both channels drop below the setting value, get < U

an

 the out 

relays will switch on.

Simultaneity of the muting inputs (MU1, MU2)

If the status of MU1, MU2 is different for more than 3 seconds the 
simultaneity fault is indicated: 
The LED "ERR" flashed code 5.

The simultaneity fault is reset only, when both inputs are low and the reset 
it operated.

Failure in feedback circuit X1-X2

As already mentioned the failure code „feedback circuit“ occurs when the 
outputs are disabled and there is no connection between terminal X1-X2. 
The LED „ERR“ flashes with failure code 4.
Also when both input signals drop now to <U

an

 and besides the open feed-

back loop no other failures are present the feedback circuit failure remains 
active and the outputs remain disabled.
If the feedback circuit is now closed and the unit is on auto reset for exter-
nal failures (see failure storing) the output relays are enable and switch on.

Potentiometer error

To achieve the required safety when adjusting the voltage threshold for 
standstill detection, ech setting function is realised with 2 potentiometers 
having one common setting knob. If on 2 corresponding potentiometers a 
different setting is detected the potentiometer error U

an

 or t

s

 is displayed.

To remove the failure please try to readjust the potentipometer. Please 
make sure that you feel the detent

Internal device failure

Internal failures are always stored, independent of the reset input X3 and 
cause the output relays immediately to switch off, the LED „UH“ to change 
it’s colour from green to red.
Examples for internal failures:

  Failure on safety relays e.g. welded output contacts

  Internal failures on measuring channels and measuring circuits

  Internal failures on control circuits for the safety relays

  failures on setting potentiometers for U

an

 and t

s

  Undervoltage failure (LED „ERR“ flashes with failure code 1)

Failure indication with flash code of LED „ERR“

The flash codes indicate failures caused externally (see diagram flashing 
codes for failure indication on page 9).
A series of flash pulses 1-7 followed by a slightly longer space is dis-
played. The flash code indicates the type of failure. If several failures are 
present at the same time only the failure with the highest priority (lowest 
flash code) is shown. When this failure is removed the other existing failu-
res are displayed in the same way according to their priority.

Failure storing / reset (terminals X2-X3)

With the external failures broken wire/offset and feedback circuit the ope-
rator can choose between manual and automatic reset after the failure is 
removed.
X2-X3 open: 

 

manual reset

X2-X3 closed: 

 

automatic reset

!

 

Attention

The a.m. storing function of the external failures broken wire /offset, 
and feedback circuit is not a safety function. I.e. in respect to safety 
aspects it can not be regarded as guaranteed. The reset for these 
failures must be therefore regarded as auto reset after removing the 
faults.

Internal device failures that could occur in seldom cases  (e.g. 
caused by temporary interference) can be reset by switching the 
supply voltage off and on. If a reset is not possible also if the voltage 
is applied correctly, the device could be defective and should be sent 
back to the manufacturer for examination or repair.

Summary of Contents for 0068412

Page 1: ...MASTER S Stillstandsw chter UG 6946 0277347 Datenblatt Betriebsanleitung DEUTSCH E DOLD S HNE KG Postfach 1251 78114 Furtwangen Deutschland Telefon 49 7723 6540 Fax 49 7723 654356 dold relays dold com...

Page 2: ...n 6 Ger te und Funktionsbeschreibung 6 Ger te und Funktionsbeschreibung 7 Anschluss des UG 6946 8 Betriebshinweise 8 Inbetriebnahme und Einstellung 9 Technische Daten 10 Standardtype 10 Bestellbeispie...

Page 3: ...en Null gefahren kann eine Entmagnetisierung des Motors stattfinden Es ist dann zu pr fen ob die verbleibende Remanenzspannung ausreicht um eine korrekte Stillstandserkennung zu gew hrleisten Bei hohe...

Page 4: ...4 UG 6946 25 11 19 de 188A...

Page 5: ...en Motoren und Anwendungen anpas senzuk nnen istdieSpannungsschwelleUan unterhalbderdasUG6946 den Stillstand erkennt einstellbar Ebenfalls einstellbar ist die Zeitdauer f r die Uan unterschritten werd...

Page 6: ...ies als Stillstand und schaltet wenn die Klemmen des R ckf hrkreises X1 X2 geschlossen sind nach der eingestellten Stillstandszeit ts die sicherheitsgerichteten Ausgangskontakte 13 14 und 23 24 ein Al...

Page 7: ...n X1 und X2 keine weiteren Fehler mehr vorliegen bleibt der Fehler R ckf hrkreis erhalten und die Ausg nge werden weiterhin nicht freigegeben Wird der R ckf hrkreis jetzt geschlossen und ist keine Spe...

Page 8: ...m Motor angeschlossen wird Zur Beachtung Wird durch Frequenzumrichter oder Sanftauslaufger te der Motorstrom allm hlich gegen Null heruntergefahren kann eine Entmagnetisierung des Motors stattfinden E...

Page 9: ...t ts blinkt die LED OUT gr n Wenn die Stillstandsfreigabe erst bei einer sehr niedrigen Umdrehungszahl des Motors erfolgen soll wird man meist Uan auf Minimum einstellen Durch eine vergr erte Einstell...

Page 10: ...ting Baubreite 22 5 mm Standardtype Eingang L1 L2 L3 Mess Motorspannung max AC 690 V Eingangswiderst nde 500 k Ansprechwert Uan 20 mV 400 mV einstellbar oder 0 2 4 V einstellbar Frequenzabh ngigkeit d...

Page 11: ...pfaden I I 1 2 I I I 2 2 2 1 2 Ger t angereiht mit Fremderw rmung durch Ger te gleicher Last 2 Kontaktreihen 1A 2x1 A 2A 2 2 2 Max Strom bei 35 C 2000 m bzw 25 C 4000 m ber Ger t freistehend 2 Kontakt...

Page 12: ...Gleichspannung erzeugen Das Ger t enth lt keine Teile die einer Wartung bed rfen Bei vorliegenden Fehlern das Ger t nicht ffnen sondern an den Hersteller zur Reparatur schicken Vorgehen bei St rungen...

Page 13: ...1 L2 L3 PE K4 K5 L1 L2 L3 X1 X2 X3 UG6946 M 3 M11887_a 0V DC24V 13 23 A1 14 24 A2 K4 K5 Motorsch tz MU1 MU2 Muting A1 On K4 K4 S11 S12 S22 13 23 33 41 S21 S33 S34 14 24 34 42 A2 Entriegelung Unlock F1...

Page 14: ...4 A2 K4 U1 W2 V1 U2 W1 V2 K5 N N DC24V 0V MU1 MU2 M11883 L1 L2 L3 N Aus F Ein Sicherung Hauptschalter N d d 18 A1 A2 28 17 27 d Stern Dreieck Zeitrelais N Netzsch tz Sternsch tz Dreiecksch tz K4 K5 UG...

Page 15: ...tandstill Monitor UG 6946 Datasheet Operating Instructions ENGLISH E DOLD S HNE KG P O Box 1251 D 78114 Furtwangen Germany Tel 49 7723 6540 Fax 49 7723 654356 dold relays dold com www dold com Transla...

Page 16: ...ndicators 20 Function 20 Function 21 Connection of UG 6946 22 Operation Notes 22 Setup and Setting 23 Technical Data 24 Standard Type 24 Ordering Example 24 Characteristic 24 Troubleshooting 25 Mainte...

Page 17: ...the motor current is run down slowly using a frequency inverter or a softstop unit a de magnetisation of the motor can take place It is necessary to check if the remaining remanence voltage is suffici...

Page 18: ...18 UG 6946 25 11 19 en 188A...

Page 19: ...erent types of motors and applications the voltage threshold indicating standstill on UG 6946 is adjustable Also the time delay between detection and energisation of the relay is adjustable standstill...

Page 20: ...rminals X1 X2 of the feedback circuit are bridged and the time delay ts is finished the safety contacts 13 14 and 23 24 close All contact paths have 2 forcibly guided contacts of 2 safety relays wired...

Page 21: ...failures are present the feedback circuit failure remains active and the outputs remain disabled If the feedback circuit is now closed and the unit is on auto reset for exter nal failures see failure...

Page 22: ...r delta starters reversing circuits multi speed motors With these applications please make sure that the measuring inputs must be linked via the motor windings An open connection will result in broken...

Page 23: ...n also be avoided by slightly increasing Uan During time delay ts the LED OUT flashes green If standstill detection shall only take place at very low speed of the motor Uan is set normally to minimum...

Page 24: ...mV Auxiliary voltage UH DC 24 V Standstill time ts 0 2 6 s Muting without muting Width 22 5 mm Standard Type Input L1 L2 L3 Measuring Motor voltage max AC 690 V Input resistance 500 k Response value U...

Page 25: ...t paths I I 1 2 I I I 2 2 2 1 2 device mounted without distance heated by devices with same load max current at over 1A 2x1 A 2A 2 contact path 2 2 2 35 C 2000 m or 25 C 4000 m device free standing ma...

Page 26: ...supply off and on The reset also takes place when both input signals rise above Uan e g when starting the motor If the simultaneity failure remains active after start of the motor e g because of short...

Page 27: ...sse z ro UG6946 Not Aus Open E Stop Auf L1 K4 L2 L3 N DC24V 0V Not Aus Modul E Stop Modul Module d arr t d urgence LG5925 M11885_b A1 31 32 13 14 X1 X2 A2 L1 L2 L3 M 3 D verrouillage Arr t d urgence O...

Page 28: ...BC7936N 13 23 L2 L1 L3 A1 14 24 A2 K4 U1 W2 V1 U2 W1 V2 K5 N N DC24V 0V MU1 MU2 M12023 L1 L2 L3 N off F on fuse main switch N d d 18 A1 A2 28 17 27 d star delta timer N mains contactor star contactor...

Page 29: ...tecteur de vitesse nulle UG 6946 Fiche Technique Manuel d utilisation FRAN AIS E DOLD S HNE KG B P 1251 78114 Furtwangen Allemagne T l 49 7723 6540 Fax 49 7723 654356 dold relays dold com www dold com...

Page 30: ...ent 34 Descriptif de l appareil et du fonctionnement 35 Branchement du d tecteur UG 6946 36 Conseils d exploitation 36 Mise en service et r glage 37 Caract ristiques techniques 38 Versions standard 38...

Page 31: ...rs de 0 par l utilisation de variateurs de fr quence ou de d marreurs ceci peut provoquer la d magnetisation du moteur Il faut alors v rifier que la tension r manente est encore suffisante pour d tect...

Page 32: ...32 UG 6946 25 11 19 fr 188A...

Page 33: ...relais de sortie est alors activ Pour pouvoir adapter l appareil la plus grande vari t de moteurs et d utilisations ce seuil de tension r siduelle Uan est r glable La temporisation de r action du rela...

Page 34: ...r ponse programm Uan le module UG 6946 l interpr te comme un arr t et quand les bornes du circuit de retour X1 X2 sont ferm es enclenche les contacts de s curit de sortie 13 14 et 23 24 la fin du tem...

Page 35: ...R affiche un clignotement de d faut selon le code 4 M me si ensuite les deux entr es de mesure indiquent des signaux Uan et que mise part l absence de liaison entre X1 et X2 aucun autre d faut ne pers...

Page 36: ...e mesure L1 L2 L3 du UG 6946 soient toujours reli s par les enroulements du moteur sinon la signalisation de d faut rupture de conducteur emp cherait la lib ration des contacts de sortie En cas de rac...

Page 37: ...intervenir qu apr s un tr s faible temps d inversion du moteur on r gle la plupart du temps Uan au minimum Une augmentation du temps ts peut alors viter une ventuelle succession d enclenchements et de...

Page 38: ...emps d arr t ts 0 2 6 s Muting sans muting Largeur utile 22 5 mm Versions standard Entr e L1 L2 L3 Tension de mesure moteur AC 690 V max R sistance d entr e 500 k seuil de r ponse Uan 20 mV 400 mV ou...

Page 39: ...I I 2 2 2 1 2 appareils accol s chauffement externe suppl mentaire par d autres appareils adjacents courant max 35 C des 2 lignes de contacts A 2x1 A 2A 1 2 2 2 2000 m resp 25 C 4000 m par appareil a...

Page 40: ...ension auxiliaire Ce d faut dispara t aussi automatiquement au red marrage du moteur quand les deux entr es de mesure L2 et L3 re oivent simultan ment des signaux de mesure sup rieurs Uan Si le d faut...

Page 41: ...G6946 Not Aus Open E Stop Auf L1 K4 L2 L3 N DC24V 0V Not Aus Modul E Stop Modul Module d arr t d urgence LG5925 M11885_b A1 31 32 13 14 X1 X2 A2 L1 L2 L3 M 3 D verrouillage Arr t d urgence Ouvert MU1...

Page 42: ...13 23 L2 L1 L3 A1 14 24 A2 K4 U1 W2 V1 U2 W1 V2 K5 N N DC24V 0V MU1 MU2 M12024 L1 L2 L3 N arr t F marche Fusible Sectionneur g n ral N d d 18 A1 A2 28 17 27 d relais toile triangle N contacteur de li...

Page 43: ...24 to 12 2 x 0 25 1 0 mm2 2 x AWG 24 to 18 A 10 mm 1 x 0 25 2 5 mm2 1 x AWG 24 to 12 2 x 0 25 1 5 mm2 mit TWIN Aderendh lse M10250 A A 7 mm 1 x 0 2 2 5 mm2 1 x AWG 24 to 12 2 x 0 2 1 5 mm2 2 x AWG 24...

Page 44: ...t 3 einmal in 3 Monaten once in 3 months une fois tous les 3 mois PL d with Cat 3 einmal pro Jahr once per year annuel nach acc to selon IEC EN 62061 IEC EN 61508 SIL CL 3 SIL 3 with HFT 1 einmal in 3...

Page 45: ...45 UG 6946 25 11 19 de en fr 188A DE EG Konformit tserkl rung EN CE Declaration of Conformity FR D claration de conformit europ enne...

Page 46: ...46 UG 6946 25 11 19 de en fr 188A DE Notizen EN Notice FR Note...

Page 47: ...47 UG 6946 25 11 19 de en fr 188A DE Notizen EN Notice FR Note...

Page 48: ...48 UG 6946 25 11 19 de en fr 188A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com Bregstra e 18 Telefon 0 77 23 654 0 Telefax 0 77 23 654 356...

Reviews: