3931182/03/01/D
Doepke
Short circuits between Dupline signal conductors and the 24 V operating voltage or con-
nections to the grounding lead to malfunction and are not allowed. The correct polarity
of operating voltage and Dupline signal conductors has to be ensured.
In order to meet the requirements for protective low voltage, VDE0100, Part 410, should
be observed and put into practice during installation.
When connecting please observe that the maximum torque of the terminals of 0.6 Nm
will not be exceeded.
The patented click-and-lock-mechanism allows an easy removal of the unit from the rail
by pushing the housing upwards until it is released.
10. Indicators
11. Technical Data
Indicator
Description
Green “BUS OK”
LED
Dupline bus:
Off - bus fault / On - bus OK
8 red LED „EIN“
All-or-nothing relay 1..8:
Off - Relay open / On - Relay closed
Min.
Typ.
Max.
Dupline
Current input
10 µA
Input channels None
Output channels 8 control channels (Switching relay outputs 1..8)
Outputs
Type All-or-nothing relay
AC
Voltage
12 VAC
250 VAC
Load capacity (per output)
100 mA
16 A
DC
Voltage
12 VDC
30 VDC
Load capacity (per output)
100 mA
10 A
Total load
80 A
Lamp loads
a
Incandescent lamps
3000 W
HV-halogen lamps
2500 W
Fluorescent lamps
2400 W
Fluorescent lamps with el. ballast
600 W
Gas discharge lamps
max. 1000 W (70µF), 1250 W (100µF
b
)
Capacitor for compensation
max. 70 µF (100µF
Energy-saving lamps, conv.
ballast
1250 W
Energy-saving lamps, el. ballast
c
300 W