11. Putting into Service
Observe the connection diagram when installing. All lines to be connected must be dead. Con-
nections between the Dupline signal and the 24V supply, or connections to earth potential, will
cause malfunctions and are not permissible.
When connecting please observe that the maximum torque of the terminals of 0.6 Nm will not
be exceeded. The patented snap-on system makes it easy to remove the device from the rail
by simply pushing the housing upwards until it disengages.
12. Indicators
13. Guarantee
All professionally installed, unaltered devices are covere d by warranty during the statutory
guarantee from the day of purchase by the end user. The guarantee is not applicable to dam-
age incurred during transport or caused by short-circuit or overloading. In the event of defects
in workmanship or material, which are discovered within the guarantee period, the company
will provide a replacement free of charge. The guarantee will be rendered null and void if the
device is opened or tampered with.
14. Technical Data
Terminal
Description
Terminal
Description
1.1
Phase input relay K1
3.1
Phase input relay K3
1.5
Output relay K1
3.5
Output relay K3
2.1
Phase input relay K2
4.1
Phase input relay K4
2.5
Output relay K2
4.5
Output relay K4
1.3
Dupline signal conductor - (D-)
1.7
Dupline signal con (D+)
1.4
0 VDC operating voltage
1.8
+24 VDC operating voltage
Indicator
Description
Green “BUS OK” LED
Dupline bus: Off: bus fault / On: bus OK
Mechanical operating lever
Switching relays 1..4:
Up: Relay closed / Down: Relay open
Min.
Typ.
Max.
Dupline
Current input
150 µA
Input channels 4 acknowledge inputs (channels 5..8)
Output channels 4 output switching signals (channels 1..4)
Operating Voltage
Rated operating voltage
21.5 VDC
24 VDC
26.5 VDC
Current input
30 mA
35 mA
130 mA
Ripple voltage
100 mV
pp
Relay outputs
Type All-or-nothing relay