6
3931169/03/05/F
Doepke
9. Putting into Service
Only an authorized expert is allowed to carry out the installation. When installing, the
connection diagram has to be observed. All conductors that shall be connected have to
be free of voltage. Following table shows the connections:
Short circuits between Dupline signal conductors and the 24 V operating voltage or con-
nections to the grounding lead to malfunction and are not allowed. The correct polarity
of operating voltage and Dupline signal conductors has to be ensured.
In order to meet the requirements for protective low voltage, VDE 0100, Part 410, should
be observed and put into practice during installation.
When connecting please observe that the maximum torque of the terminals of 0.6 Nm
will not be exceeded.
The patented click-and-lock-mechanism allows an easy removal of the unit from the rail
by pushing the housing upwards until it is released.
10. Indicators
11. Technical Data
Terminal
Description
Terminal
Description
1.1/1.5 Motor 1 output (UP/
DOWN
)
1.2/1.6 Motor 1 phase input (L
IN1
)
2.1/2.5 Motor 2 output (
DOWN
/UP)
2.2/2.6 Motor 2 phase input (L
IN2
)
1.3
Dupline signal conductor - (D-)
1.7
Dupline signal con (D+)
1.4
0 VDC operating voltage
1.8
+24 VDC operating voltage
Indicator
Description
Green “BUS OK”
LED
Dupline bus:
Off - bus fault / On - bus OK
2 red LED „AUF“
All-or-nothing relay 1 / 2:
Off - no upward movement / On - upward movement
2 red LED „AB“
All-or-nothing relay 1 / 2:
Off - no downward movement / On - downward movement
Min.
Typ.
Max.
Dupline
Current input
10 µA
Input channels None
Output channels 4 control channels (shutters 1/2, each „Up“ und
„Down“)
Outputs
Type All-or-nothing relay
Voltage
230 VAC
Rated current / load capacity
2 A
Power factor
cos
ϕ
= 0.6 - 1