TDR9000
™
Circuit Breaker Test System User’s Guide
72A-1898 Rev. A 11/01
3-23
Monday
, November 26, 2001 1:09 pm
Trip/Close Module
The Trip/Close control function consists of two parts:
• The Trip/Close control module located inside the TDR9000
• The connector, fuses and protection circuits that are part of the
TDR9000 System module.
The Trip/Close module enables the TDR9000 to control the following
tests:
• Trip
• Close
• Trip Free – Standing
• Trip Free – Delay
• Trip Free – Contact 1 Make
• Reclose – Standing
• Reclose – Delay
• O-C-O Standing
• O-C-O Delay
• O-C-O Contact 1 Make
This module operates the circuit breaker under test through the action
of solid-state switches that Trip or Close the circuit breaker and is
polarity-insensitive, so that the user need not know lead polarity.
The TDR9000 can be ordered without the Trip/Close module, however,
all tests need to be triggered externally to the TDR9000 using a push
button or through SCADA.
Summary of Contents for TDR9000
Page 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...