6
738I ITI™ Installation and Programming Guide | Digital Monitoring Products, Inc.
Wire the Module
The 738I connects to the panel 4-wire keypad data bus of XT30/XT50 Series panels
and panel 4-wire keypad data bus and the LX-Bus™ of XR150/XR550 Series panels.
Use a 4-wire harness to easily connect the 738I to an ITI Wireless Receiver.
Note:
When programming 738I zones on the LX-Bus of an XR150/XR550 Series
panel, select
NO
when prompted whether the zone is wireless.
DMP Bus Header
For connection to a keypad bus, connect the provided Model 300 4-wire harness
(with one 4-wire connector) from the DMP BUS header to the panel terminals marked
Red (7), Yellow (8), Green (9), and Black (10).
For connection to the LX-Bus, connect the provided Model 300 4-wire harness from
the DMP BUS header to the four wires of the LX-Bus.
Receiver Header
Connect the provided Model 300 4-wire harness from the RECEIVER header to the ITI
wireless receiver.
Red = +12
Green = B
Yellow = A
Black = GND
2
Summary of Contents for ITI 738I
Page 1: ...INSTALLATION AND PROGRAMMING GUIDE 738I ITI Interface Module...
Page 2: ......
Page 4: ......
Page 22: ...18 738I ITI Installation and Programming Guide Digital Monitoring Products Inc...
Page 23: ......
Page 24: ...LT 0415 20161 2020 Digital Monitoring Products Inc...