iCom Series Universal Alarm Communicator Programming and Installation Guide
Digital
Monitoring
Products
9
Ademco/Honeywell ECP Connection
The communicator can be connected to the ECP Bus of an Ademco/Honeywell panel. See Table 3 and Figure 8 for the
necessary wiring connections for the iComSL to communicate with the Ademco/Honeywell ECP Bus.
Communicator to ECP Wiring
Communicator
Ademco/Honeywell ECP Bus
+12
Keypad Power
G
Keypad GND
Z4+
Data Out
Z4‑
Data In
Table 3: Communicator to Ademco/Honeywell ECP Wiring
S N
+DC- Z1 Z2 Z3 G +Z4- 01 02 T1 R1 T2 R2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
+
+
-
HI
HI
HI
LO
LO
LO
LO
HI
HI
LO
LO
HI
HI
LO
LO
HI
TIP
(BROWN)
RING
(GRAY)
TIP
(GREEN)
RING
(RED)
+
-
BLACK
RED
SYNC
COM
DATA
Use SA4120XM-1 Cable
1 2 3 4 5 6 7 8
OUT 17
+12 A
U
X
GND
OUT 18
VISTA 20P ONLY
Ademco Vista 20P
Figure 8: Communicator to Ademco Vista 20P ECP Wiring
The communicator provides the following operation when connected to the ECP Bus of an Ademco/Honeywell panel:
• Arm and disarm the Ademco/Honeywell panel using the Virtual Keypad app and browser (Stay/Away systems
only).
• Receive alarm, trouble, opening/closing, and other messages from the panel and send them to the central
station SCS‑1R or SCS‑VR receivers.
• Add, delete, and change user codes in the Ademco/Honeywell panel.
ECP operation must be enabled in the iComSL. See Keypad Input in System Options for additional information.
Accessing Programming on the Ademco/Honeywell Panel
The installer code may be changed in Ademco/Honeywell panels and a new 4‑digit code may be entered.
If the installer code is not known, use the following steps to access programming in the Ademco/Honeywell panel
without an installer code:
1. Power down and then power up the Ademco/Honeywell panel.
2. Within 1 minute of powering up the Ademco/Honeywell panel, simultaneously press and hold the # and *
buttons on the keypad.
3. The keypad displays PROGRAMMING.
Configuring Communication with the Ademco/Honeywell Panel
The following steps describe how to configure Ademco/Honeywell control panels to communicate with the
communicator.
1. Program Position * 54: Enter 0. This enables no signaling delay.
2. Program Position * 55: Enter 1. This enables communication to the communicator.
3. Program Position * 65: Enter 0. This disables opening reports.
4. Program Position * 66: Enter 0. This disables closing reports.
5. Program Position * 84: Enter 0. This disables CP01 and allows remote Arm Away.
6. Program Position * 193: Enter 1 0. This enables the iComSL ECP Bus address.
If the Ademco/Honeywell panel fails to communicate with the communicator, program Position * 29 to enable the
long range radio on the Ademco/Honeywell panel.