![DMP Electronics iComSL Programming And Installation Manual Download Page 10](http://html1.mh-extra.com/html/dmp-electronics/icomsl/icomsl_programming-and-installation-manual_2513829010.webp)
Digital
Monitoring
Products
iCom Series Universal Alarm Communicator Programming and Installation Guide
8
Use 18-22 AWG
for Power Supply
connection
Z4
+
Z4
-
DMP Panel
MODEL iComSL
PROG
+12
G
Z1
Z2
Z4-
Z4+
G
Z3
R
T
O2
O1
R
B
J8
J9
S3
12 VDC Aux. Output
+
-
Use 18-22 AWG
for Power Supply
connection
Z4
+
Z4
-
ADEMCO Panel
MODEL iComSL
PROG
+12
G
Z1
Z2
Z4-
Z4+
G
Z3
R
T
O2
O1
R
B
J8
J9
S3
12 VDC Aux. Output
+
-
BELL -
12 VDC BELL +
Use 18-22 AWG
for Power Supply
connection
Z4
+
Z4
-
NAPCO Panel
MODEL iComSL
PROG
+12
G
Z1
Z2
Z4-
Z4+
G
Z3
R
T
O2
O1
R
B
J8
J9
S3
12 VDC Aux. Output
+
-
BELL -
12 VDC BELL +
Use 18-22 AWG
for Power Supply
connection
Z4
-
DSC Panel
MODEL iComSL
PROG
+12
G
Z1
Z2
Z4-
Z4+
G
Z3
R
T
O2
O1
R
B
J8
J9
S3
12/24 VDC Aux. Output
+
-
BELL -
12/24 VDC BELL +
10k ohm
1k ohm (for Supervision)
1k ohm
1k ohm
1k ohm
1k ohm (for Supervision)
2.2k ohm (for Supervision)
Program Zone 4
DO - Alarm
AO - Alarm
Voltages above 1.4 VDC
are considered Alarm
Voltages above 1.4 VDC
are considered Alarm
Voltages above 1.4 VDC
are considered Alarm
Voltages below 0.7 VDC
are considered Alarm
Use 18-22 AWG
for Power Supply
connection
Z4
+
Z4
-
24VDC Panel
MODEL iComSLF
PROG
+12
G
Z1
Z2
Z4-
Z4+
G
Z3
R
T
O2
O1
R
B
J8
J9
S3
12/24 VDC Aux. Output
+
-
BELL -
24 VDC BELL +
4.7k ohm (for Supervision if required)
1k ohm
Voltages above 1.4 VDC
are considered Alarm
1k ohm
Figure 7: Zone 4 Bell Connection