7000 Series Installation and Programming Guide | Digital Monitoring Products
12
CUSTOM CARD FORMAT
Custom card format programming options are only available on 7063/A, 7073/A, 7163, and 7173 keypads.
Card Formats
Select
DMP
to allow credentials that use a 26-45 bit data string. The menu advances
to
REQUIRE SITE
.
Select
CUSTOM
to disable DMP format and program slots 1-8 as needed. The menu
advances to
FORMAT NO
.
Select
ANY
to allow all Wiegand card reads to activate the door strike relay. The door
strike relay is activated for the length of time programmed in
ZN 3 REX TIME
. No user
code information is sent to the panel. The menu advances to
NO COMM WITH PNL
.
The default card format is
DMP
.
Card Format Number
Select the slot number (1-8) that you want to program for a custom non-DMP card
format. The format that is programmed into slot 1 is the default format. In the event
that a card with an unrecognized format is used, that card will be read in the format
that is programmed in slot 1. To restrict card reads to specific formats, only program
slots 2-8.
See Public Card Formats for some publicly available card formats that can be used
with the keypad. Other private or custom formats may also be compatible. Please
contact the credential supplier or manufacturer for the bit structure.
Note:
If you select slot 1 and you are upgrading from XR panel version 182 or
earlier,
FORMAT NAME
will automatically be named
SINGLE CARD FORMAT
and
WIEGAND CODE LENGTH
will default to 45.
Format Name
Press any select key to rename the card format. Press
CMD
to save and advance.
Wiegand Code Length
When using a custom credential, enter the total number of bits to be received in
Wiegand code including parity bits.
Press any select key or area to enter a number between 1-255 to equal the number of
bits. Default is
26
bits.
An access card contains data
bits for a site code, user code,
and start/stop/parity bits. The
starting position, location,
and code length must be
determined and programmed
into the keypad. See Figure 8.
CARD FORMATS
DMP
CUSTOM ANY
CARD FORMATS
FORMAT NO: -
FORMAT NAME
*UNUSED*
WIEGAND CODE
LENGTH:
26
0 1 1 1 0 1 0 1 1 0 1 1 0 1 0 1 0 0 0 1 1 0 0 1 1 1
First Bit
Received
Position = 0
Site Code
Position = 1
Length = 8
User Code
Position = 9
Length = 16
Last Bit
Received
Position = 25
Example:
Wiegand Code Length = 26 bits
Figure 8: Wiegand Data Stream Bit Location