INSTALLATION GUIDE
867 Style W
LX-Bus Notification Module
Page 1: ...INSTALLATION GUIDE 867 Style W LX Bus Notification Module...
Page 2: ...ides ground fault open and short condition supervision on the notification circuit The module has four LEDs to indicate circuit trouble and ground fault conditions as well as power supply and data mon...
Page 3: ...he duration of the bell cutoff time or until manually silenced by an authorized user Set the Supervisory Zone Address Supervisory Address switches allow you to set the zone address for the module whic...
Page 4: ...panel LX Bus Figure 2 Ring Style Header Detail Steady Pulse Temporal California Schools RING STYL Table 2 Bell Ring Style Options JUMPER SETTING BELL CADENCE Steady On for duration of Bell Cutoff tim...
Page 5: ...r supply output positive connects to module Terminal 1 and power supply output negative connects to module Terminal 2 The power supply must be supervised and provide a set of Normally Closed trouble c...
Page 6: ...rent LX Bus 30 mA maximum Bell Power 30 mA standby 86 mA maximum Alarm Switching Current 5 Amps 12 or 24 VDC CERTIFICATIONS California State Fire Marshal CSFM FCC Certified Part 15 New York City FDNY...
Page 7: ...nce to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television recepti...