SuperSigma2 AM PMS
–
V1.5.6 17-1-2020
Page 61 (97)
©2019 DMC GmbH Herten Germany
M3-13P
Line Contactor Coil holding voltage ”LCHoldVl”
It sets the line contactor coil holding voltage applied when the line contactor is closed and 1 s of time is elapsed. It is
expressed as percentage of the
in the BDI menu.
Example:
is set to 48V and the desired line contactor coil holding voltage is 24V.
The percentage to set in the
Line Contactor Coil holding voltage ”LCHoldVl””
has to be 100%*24V / 48V = 50%.
If it set to 100% the full battery voltage will be applied
M3-14P
Digital Output 2 pull-
in voltage ”Do2PlInV”
It sets the Digital Output 2 pull in voltage
applied for 1s. It is expressed as percentage of the “
”” in the BDI menu.
If it set to 100% the full battery voltage will be applied.
M3-15P
Digital Output 2
hold voltage ”Do
2HoldV
”
It sets the Digital Output 2 holding voltage applied when the line contactor is closed and 1 s of time is elapsed. It is
expressed as percentage of the “
”” in the BDI menu.
If it set to 100% the full battery voltage will be applied.
M3-16P
Digital Output 3 pull-
in voltage ”Do
3PlInV
”
It sets the Digital Output 3 pull in voltage applied fo
r 1s. It is expressed as percentage of the “
”” in the BDI menu.
If it set to 100% the full battery voltage will be applied.
M3-17P
Digital Output 3
hold voltage ”Do3HoldV”
It sets the Digital Output 3 holding voltage applied when the line contactor is closed and 1 s of time is elapsed. It is
expressed as percentage of the
in the BDI menu.
If it set to 100% the full battery voltage will be applied.
M3-18P
Driver output 2 configuration “Drv2Cfg”
This sets the configuration for Driver Output 2.
•
If set to
0
, no function is assigned to digital output driver 2 (pin 16 in 35 way connector)
•
If set to
1
, digital output 2 is activated if motor temperature is higher than threshold “
Temperature threshold (for output driver)
“MotTmpTh”” and deactiv
ated when motor temperature gets lower
than threshold “
M3-21T Motor Temperature threshold (for output driver)
- 8 °C of hysteresis.
•
If set to
2
, digital output 2 is activated if controller temperature is higher than threshold “
output driver) “CtrTmpTh””, and deactivated when controller temper
ature gets
lower than threshold “
M3-22T Controller Temperature threshold (for
- 8 °C of
hysteresis .
•
If set to
3
, digital output 2 is activated if motor temperature is higher than threshold “
Temperature threshold (for output driver)
OR if controller temperature is higher than threshold
M3-22T Controller Temperature threshold (for
output driver) “CtrTmpTh””, while it is deactivated when motor
temperature gets lower than threshold “
M3-21T Motor Temperature threshold (for output driver)
- 8 °C of hysteresis AND
controller temperature gets lower than threshold “
- 8 °C of hysteresis.