FT7000, RACK MONITOR MANUAL 11033PA-ATEX
Managing Bypass Cards
The FT7000 Rack Monitor will come from the factory with two Ground Bypass cards and two Overfill
bypass cards paired to the monitor. These cards do not require pairing and will work with the monitor
out of the box.
If a card needs to be added, removed, or replaced, the monitor must be put into pairing mode. Entering
pairing mode for any reason will remove all currently paired bypass cards. It will be necessary to re-pair
ALL bypass cards if the monitor is put into pairing mode.
1.
Begin by powering off the rack monitor.
2.
Remove the 12 lid screws and open the lid to access the configuration switches.
3.
Move the ‘NEW TAG’ switch to the right(ON) position.
4.
Close the rack monitor lid.
5.
Restore power to the rack monitor.
6.
One at a time, place a bypass card in front of the bypass indicator on the monitor, then remove
the card.
7.
With each successive swipe of the card, the bypass indicator will cycle blue -> red -> off -> blue…
The blue bypass light indicates that the card is recognized as a ground bypass card, while the red
bypass light indicates the card is recognized as an overfill bypass card.
8.
Repeat step 7 with all bypass cards to be used with the monitor.
9.
Remove power from the rack monitor.
10.
Open the lid to access the configuration switches.
11.
Move the ‘NEW TAG’ switch to the left(OFF) position.
12.
Close the rack monitor lid.
13.
Screw in the 12 lid screws.
14.
Restore power to the rack monitor.