7. INSTALLATION AND MOUNTING 

Instruments 

XR160C

XR170C

XR162C

 and 

XR172C

 shall be mounted on panel, in a 29x71 mm hole, and 

fixed using the special bracket supplied. 

XR160D

XR170D

 and slave modules 

XR30SL

 and 

XR40SL

 shall be 

mounted on an omega DIN rail. The instruments provided with a slave module shall be connected through the 
special multipolar cable supplied. 
The temperature range allowed for correct operation is 0 - 60 °C. Avoid places subject to strong vibrations, 
corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. Let air circulate by 
the cooling holes. 

8. ELECTRICAL CONNECTIONS 

The instruments are provided with screw terminal block to connect cables with a cross section up to 2,5 mm

2

Before connecting cables make sure the power supply complies with the instrument’s requirements. Separate 
the probe cables from the power supply cables, from the outputs and the power connections. Do not exceed 
the maximum current allowed on each relay, in case of heavier loads use a suitable external relay. 
Instruments 

XR162C

 and 

XR172C

 are connected to slave modules 

XR30SL

 and 

XR40SL

, respectively, 

through a multipolar connector (included). They accommodate the instrument relays and the transformer 
powering the whole system. 

8.1 Probes connection 

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is 
recommended to place the thermostat probe away from air streams to correctly measure the average room 
temperature. Place the defrost termination probe among the evaporator fins in the coldest place, where most 
ice is formed, far from heaters or from the warmest place during defrost, to prevent premature defrost 
termination. 

9. ALARM SIGNALS 

Message - Mode 

Cause 

Outputs 

“EE”  

Flashing 

Data or memory failure 

Alarm output ON; Other outputs unchanged 

“P1” 

Flashing 

Thermostat probe failure 

Alarm output ON; Compressor output 
according to parameters “COn” and “COF” 

“P2” Alternating 

 

 

with room temperature 

Evaporator probe failure 

Alarm output ON; Other outputs unchanged; 
End defrost is timed 

“HA” Alternating 

 

 

with room temperature 

Maximum temperature 
alarm 

Alarm output ON; Other outputs unchanged.

“LA” Alternating 

 

 

with room temperature 

Minimum temperature alarm Alarm output ON; Other outputs unchanged.

“dEA” Alternating 

 

 

with room temperature 

Defrost timeout alarm 

Alarm output ON; Other outputs unchanged.

“FF” Alternating 

 

 

with room temperature 

Fast freezing  interrupted by 
power failure 

Alarm output ON; Other outputs unchanged.

9.1  Silencing buzzer / alarm relay output  

Once the alarm signal is detected the buzzer and the alarm output can be disabled by pressing any key 
according to the ALC par. 
With ALC=0 or 1 buzzer and alarm relay are silenced by pressing any key 
With ALC=2 or 3 the buzzer is silenced by pressing a key, the alarm relay remains activated as long as the 
alarm condition lasts. 
The display signal remains as long as the alarm condition remains.  
 
 

 

952057-58

 

XR160C - XR170C - XR160D - XR170D - XR162C - XR172C 

7/

י

 

 

Summary of Contents for XR160C

Page 1: ...________________ 4 5 1 Function Menu_______________________________________________________ 4 5 2 List of functions ______________________________________________________ 4 5 3 Exit Timeout___________...

Page 2: ...eful 2 GENERAL DESCRIPTION Models XR160C and XR170C 32x74 mm format are microprocessor based controllers suitable for applications on medium or low temperature refrigerating units They are provided wi...

Page 3: ...ing defrost After defrost there is a timed fan delay allowing for drip time set by means of the Fnd parameter FnC 2 fans will switch ON and OFF with the compressor and run during defrost FnC 3 fans wi...

Page 4: ...le LED MODE Function ON Compressor enabled FLASHING Programming Phase flashing with LED Anti short cycle delay enabled ON Fan enabled FLASHING Programming Phase flashing with LED ON Defrost enabled FL...

Page 5: ...put into Pr1 user level by pressing SET DOWN When a parameter is present in Pr1 LED is on 5 5 Changing a parameter s value Each parameter is identified by a special alphanumeric code label To change...

Page 6: ...hich causes the end of defrost dFd Temperature displayed during defrost 0 real temperature 1 temperature at defrost start 2 set point 3 dEF label dAd MAX display delay after defrost 0 120 min Sets the...

Page 7: ...iquid infiltration It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature Place the defrost termination probe among the evaporator fins...

Page 8: ...starts Alarms dEA and FF automatically stop after 30 minutes 10 TECHNICAL DATA Housing self extinguishing ABS Case XR160C XR162C XR172C frontal 32x74 mm depth 60mm XR170C frontal 32x74 mm depth 70mm X...

Page 9: ...172C buzzer for an acoustic signal of alarms Data storing on the non volatile memory EEPROM Operating temperature 0 60 C Relative humidity 20 85 no condensing Storage temperature 30 85 C Measuring and...

Page 10: ...F 1 120 Pr2 6 dSd 1 120 Pr2 0 MdF 0 120 Pr2 30 dtE 57 50 C o 196 F Pr2 8 46 dFd 0 Real 1 Start 2 Set 3 dEF Pr2 1 dAd 0 120 Pr2 30 tdF 0 Eletrical 1 Hot gas Long Time 2 Relay OFF 3 Relay ON Short time...