Dixell

 

Installing and Operating Instructions

 

release  7.0

 

12.  DEFAULT SETTING VALUES - STANDARD MODELS 

 

P

ARAMETER

 

R

ANGE

 

L

EVEL

  D

EFAULT

 

°C/°F

 

 

Set 

LS ÷ US 

Pr1 

-5/0 

HY 

0,2÷12°C / 2÷120°F 

Pr1 

2/4 

LS 

  -57 ÷ Set 

Pr2 

-30/-22 

US 

Set ÷ 99°C / 196°F 

Pr2 

20/68 

AC 

0 ÷ 30 

Pr2 

ALC 

0 o 2=rel (0 ÷50); 1o 3=absolute 

Pr2 

ALU 

0÷50°C or 90°F /ALL ÷  99°C / 196°F  

Pr2 

10/20 

ALL 

 0÷50°C or 90°F / -57÷  ALU  

Pr2 

10/20 

ALd 

0 ÷ 120 

Pr2 

15 

dAO 

0 ÷ 720 

Pr2 

90/180 

OdS 0÷120 Pr2 

CCt 

0 ÷ 990 

Pr2 

240 

dAF 

0 ÷ 120 

Pr2 

120 

IdF 

1 ÷ 120 

Pr2 

dSd 

1 ÷ 120 

Pr2 

MdF 

0 ÷ 120 

Pr2 

30 

dtE 

-57 ÷50°C o 196°F  

Pr2 

8/46 

dFd 

0=Real, 1=Start, 2=Set, 3=dEF 

Pr2 

dAd 

0 ÷ 120 

Pr2 

30 

tdF 

0=Eletrical, 1=Hot gas (Long Time); 2= Relay OFF; 3=Relay ON (Short time) 

Pr2 

EdF 

0=Not present, 1= Evap. Probe present 

Pr2 

Fdt 

0 ÷ 120 

Pr2 

dPO 

0=Immediately - 1=Normal 

Pr2 

FnC 

OFF during defrost: 0=with compressor;  1=Continuously  

ON during defrost: 2=with compressor;  3=Continuously;  

4=As 2° compressor 

Pr2 1 

FSt 

-60 ÷ 50°C / 122°F 

Pr2 

2/35 

Fnd 

0 ÷ 120 

Pr2 

10 

Ot -12÷12°C; 

-120÷120°F 

Pr2 

OE -12÷12°C; 

-120÷120°F 

Pr2 

CF 

    0=°Celsius 1=°Fahrenheit 

Pr2 

0/1 

COn 

0 ÷ 120 

Pr2 

15 

COF 

0 ÷ 120 

Pr2 

30 

 

 

952057-58

 

XR160C - XR170C - XR160D - XR170D - XR162C - XR172C 

10/

י

 

 

Summary of Contents for XR160C

Page 1: ...________________ 4 5 1 Function Menu_______________________________________________________ 4 5 2 List of functions ______________________________________________________ 4 5 3 Exit Timeout___________...

Page 2: ...eful 2 GENERAL DESCRIPTION Models XR160C and XR170C 32x74 mm format are microprocessor based controllers suitable for applications on medium or low temperature refrigerating units They are provided wi...

Page 3: ...ing defrost After defrost there is a timed fan delay allowing for drip time set by means of the Fnd parameter FnC 2 fans will switch ON and OFF with the compressor and run during defrost FnC 3 fans wi...

Page 4: ...le LED MODE Function ON Compressor enabled FLASHING Programming Phase flashing with LED Anti short cycle delay enabled ON Fan enabled FLASHING Programming Phase flashing with LED ON Defrost enabled FL...

Page 5: ...put into Pr1 user level by pressing SET DOWN When a parameter is present in Pr1 LED is on 5 5 Changing a parameter s value Each parameter is identified by a special alphanumeric code label To change...

Page 6: ...hich causes the end of defrost dFd Temperature displayed during defrost 0 real temperature 1 temperature at defrost start 2 set point 3 dEF label dAd MAX display delay after defrost 0 120 min Sets the...

Page 7: ...iquid infiltration It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature Place the defrost termination probe among the evaporator fins...

Page 8: ...starts Alarms dEA and FF automatically stop after 30 minutes 10 TECHNICAL DATA Housing self extinguishing ABS Case XR160C XR162C XR172C frontal 32x74 mm depth 60mm XR170C frontal 32x74 mm depth 70mm X...

Page 9: ...172C buzzer for an acoustic signal of alarms Data storing on the non volatile memory EEPROM Operating temperature 0 60 C Relative humidity 20 85 no condensing Storage temperature 30 85 C Measuring and...

Page 10: ...F 1 120 Pr2 6 dSd 1 120 Pr2 0 MdF 0 120 Pr2 30 dtE 57 50 C o 196 F Pr2 8 46 dFd 0 Real 1 Start 2 Set 3 dEF Pr2 1 dAd 0 120 Pr2 30 tdF 0 Eletrical 1 Hot gas Long Time 2 Relay OFF 3 Relay ON Short time...

Reviews: