                           XR03CX – XR04CX 

1/3 

 

DIGITAL CONTROLLER 

XR03CX – XR04CX 

1  CONTENTS 

1.

 

Contents ____________________________________________________________________________ 1

 

2.

 

General warnings _____________________________________________________________________ 1

 

3.

 

General description ___________________________________________________________________ 1

 

4.

 

Regulation  __________________________________________________________________________ 1

 

5.

 

Defrost _____________________________________________________________________________ 1

 

6.

 

Front panel commands  ________________________________________________________________ 1

 

7.

 

Parameters __________________________________________________________________________ 2

 

8.

 

Digital inputs _________________________________________________________________________ 2

 

9.

 

Installation and mounting _______________________________________________________________ 2

 

10.

 

Electrical connections  _________________________________________________________________ 2

 

11.

 

How to use the hot key_________________________________________________________________ 2

 

12.

 

Alarm signalling ______________________________________________________________________ 2

 

13.

 

Technical data _______________________________________________________________________ 3

 

14.

 

Connections _________________________________________________________________________ 3

 

15.

 

Default setting values __________________________________________________________________ 3

 

 

2  GENERAL WARNING 

2.1

 

PLEASE READ BEFORE USING THIS MANUAL 

1.

 

This manual is part of the product and should be kept near the instrument for easy and quick 

reference. 

2.

 

The  instrument  shall  not  be  used  for  purposes  different  from  those  described  hereunder.  It 

cannot be used as a safety device. 

3.

 

Check the application limits before proceeding. 

4.

 

Dixell  Srl  reserves  the  right  to  change  the  composition  of  its  products,  even  without  notice, 

ensuring the same and unchanged functionality. 

2.2

 

SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding 

sudden  temperature  changes  with  high  atmospheric  humidity  to  prevent    formation  of 

condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In  case  of  failure  or  faulty  operation  send  the  instrument  back  to  the  distributor  or  to  “Dixell 

S.r.l.” (see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough 

from each other, without crossing or intertwining. 

 

In  case  of  applications  in  industrial  environments,  the  use  of  mains  filters  (our  mod.  FT1) in 

parallel with inductive loads could be useful. 

3  GENERAL DESCRIPTION 

The 

XR03CX

, in 

32

74x50mm short format

, is microprocessor based controller suitable for applications on 

normal temperature refrigerating units. It provides two relay output: one for compressor and the other one for 
alarm signalling or as auxiliary output. It provides an NTC probe input and a digital input for alarm signalling, 
for  switching  the  auxiliary  output  or  for  start  defrost.  The  instrument  is  fully  configurable  through  special 
parameters that can be easily programmed through the keyboard or the by HOTKEY. 

 

The 

XR04CX

, in 

32

74x50mm short format

, is microprocessor based controller suitable for applications on 

normal or low temperature refrigerating units. It provides two relay output: one for compressor and the other 
one for defrost. It provides two NTC probe inputs, one for room temperature and other one to control defrost 
termination. The instrument is fully configurable through special parameters that can be easily programmed 
through the keyboard or the by HOTKEY. 

4  REGULATION 

The  regulation  is  performed  according  to 

the  temperature  measured  by  the 

thermostat  probe  with  a  positive 

differential  from  the  set  point:  if  the 

temperature  increases  and  reaches  set 

point  plus  differential  the  compressor  is 

started  and  then  turned  off  when  the 

temperature  reaches  the  set  point  value 

again. 

 

In  case  of  fault  in  the  thermostat  probe  the  start  and  stop  of  the  compressor  are  timed  through 

parameters “

Cy

” and “

Cn

”. 

5  DEFROST 

5.1

 

XR03CX 

 

Defrost is performed through a simple stop of the compressor. Parameter “i

d

” controls the interval 

between defrost cycles, while its length is controlled by parameter “

Md

”. 

5.2

 

XR04CX 

 

Two defrost modes are available through the “

td

” parameter: 

 

td=EL

 

 

defrost through electrical heater (compressor OFF) 

 

td=in 

 

hot gas  defrost (compressor ON).  

Other parameters are used to control the interval between defrost cycles (

id

) ), its maximum length 

(

Md

)  and  two  defrost modes:  timed  or controlled  by  the  evaporator’s  probe.  At  the  end  of  defrost 

dripping time is started, its length is set in the 

dt

 parameter. With 

dt=0

 the dripping time is disabled. 

 

6  FRONT PANEL COMMANDS 

 

  

To  display  target  set  point,  in 

programming mode it selects a 

parameter  or  confirm  an 

operation 

 

To start a manual defrost  

 

In  programming  mode  it 

browses  the  parameter  codes 

or  increases  the  displayed 

value 

 AUX

 

In  programming  mode  it 

browses  the  parameter  codes 

or  decreases  the  displayed 

value 

 

KEYS COMBINATION 

 

 

+

 

 

To lock or unlock the keyboard

 

 

+

 

 

To enter in programming mode 

 

+

 

 

To return to room temperature display

 

 

LED 

MODO 

SIGNIFICATO 

 

On 

Compressore enabled 

Flashing 

Anti short cycle delay enabled (AC parameter) 

 

On 

Defrost in progress 

Flashing 

Dripping in progress 

 

On 

Measurement unit  

Flashing 

Programming mode 

 

On 

Measurement unit 

Flashing 

Programming mode 

6.1

 

HOW TO SEE THE SET POINT 

 

1.

 

Push and immediately release the 

SET 

key, the set point will be showed; 

2.

 

Push and immediately release the 

SET

 key or wait about 5s to return to normal visualisation. 

6.2

 

HOW TO CHANGE THE SETPOINT 

 

1.

 

Push the SET key for more than 2 seconds to change the Set point value; 

2.

 

The value of the set point will be displayed and the “°C” or “°F” LED starts blinking; 

3.

 

To change the Set value push the   or    arrows within 10s. 

4.

 

To memorise the new set point value push the SET key again or wait 10s. 

6.3

 

HOW TO START A MANUAL DEFROST 

 

Push the 

DEF 

 key for more than 2 seconds and a manual defrost will start 

6.4

 

HOW TO CHANGE A PARAMETER VALUE 

 

To change the parameter’s value operate as follows:  

1.

 

Enter  the  Programming  mode  by  pressing  the 

SET

  keys  for  3s  (“

°C”  or  “°F”

  LED  starts 

blinking). 

2.

 

Select the required parameter. Press the “

SET

” key to display its value 

3.

 

Use   or   to change its value. 

4.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET

+   or wait 15s without pressing a key. 

NOTE

: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

6.5

 

HIDDEN MENU 

The hidden menu includes all the parameters of the instrument. 

HOW TO ENTER THE HIDDEN MENU 

1.

 

Enter  the  Programming  mode  by  pressing  the 

SET

  keys  for  3s  (“

°C”  or  “°F”

  LED  starts 

blinking). 

2.

 

Released the keys, then push again the 

SET

 keys for more than 7s. The L2 label will be 

displayed immediately followed from the Hy parameter.  

NOW YOU ARE IN THE HIDDEN MENU.

 

3.

 

Select the required parameter. 

4.

 

Press the “

SET

” key to display its value 

5.

 

Use   or   to change its value. 

6.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET

+   or wait 15s without pressing a key. 

NOTE1: 

if none parameter is present in L1, after 3s the “nP” message is displayed. Keep the keys 

pushed till the L2 message is displayed.  

NOTE2

: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

HOW  TO  MOVE  A  PARAMETER  FROM  THE  HIDDEN  MENU  TO  THE  FIRST 
LEVEL AND VICEVERSA. 

Each  parameter  present  in  the  HIDDEN  MENU  can  be  removed  or  put  into  “THE  FIRST  LEVEL” 

(user level) by pressing 

SET

+  . In HIDDEN MENU when a parameter is present in First Level the 

decimal point is on. 

6.6

 

TO LOCK THE KEYBOARD 

 

Keep pressed for more than 3s the   and   keys. 

The “

OF

” message will be displayed and the keyboard will be locked. If a key is pressed more than 

3s the “OF” message will be displayed. 

6.7

 

TO UNLOCK THE KEYBOARD 

 

Keep pressed together for more than 3s the   and   keys till the 

“on” 

message will be displayed. 

 

 

 

 