Installing and Operating Instructions

rel.1.0 - cod. 1592009261

PR 1592009260 XW60L GB r1.0 20.03.02.doc

                           

XW60L – XW60V

1/4

W

ING

XW60L – XW60V

1.

 

GENERAL WARNING

1.1

 

PLEASE READ BEFORE USING THIS MANUAL

 

This manual is part of the product and should be kept near the instrument for easy and quick reference.

 

The instrument shall not be used for purposes different from those described hereunder. It cannot be used
as a safety device.

 

Check the application limits before proceeding.

1.2

 

 SAFETY PRECAUTIONS

 

Check the supply voltage is correct before connecting the instrument.

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden
temperature changes with high atmospheric humidity to prevent  formation of condensation

 

Warning: disconnect all electrical connections before any kind of maintenance.

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened.

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell s.r.l.” (see
address) with a detailed description of the fault.

 

Consider the maximum current which can be applied to each relay (see Technical Data).

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from each
other, without crossing or intertwining.

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with
inductive loads could be useful.

2.

 

GENERAL DESCRIPTION

Model 

XW60L

38x185

 mm format, and model 

XW60V,

 

100x64 

format,  are microprocessor based controllers

suitable for applications on medium or low temperature refrigerating units. They are provided with four relay
outputs to control compressor, defrost - which can be either electrical or hot gas  - the evaporator fans and the
lights. They are also provided with 2 NTC or PTC probe inputs, one for temperature control, one to control the
defrost end temperature of the evaporator. There are 1 digital inputs (free contact) configurable by parameter.
An output allows the user to programme the parameter list with the 

“Hot Key”.

3.

 

CONTROLLING LOADS

3.1

 

THE COMPRESSOR

The regulation is performed according to the temperature measured by the thermostat probe with a positive
differential from the set point: if the temperature increases and reaches set point plus differential the compressor
is started and then turned off when the temperature reaches the set point value again.
In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters

COn

” and “

COF

”.

3.2

 

FAST FREEZING

When defrost is not in progress, it can be activated the keypad by holding the 

o

 key pressed for about 3

seconds. The compressor operates in continuous mode for the time set through the “

CCt

” parameter. The cycle

can be terminated before the end of the set time using the same activation key, 

o

 for about 3 seconds.

3.3

 

DEFROST

Two defrost modes are available through the “

tdF

” parameter: defrost with electrical heater or hot gas. The

defrost interval is control by means of parameter “

EdF

”: (EdF=in) the defrost is made every “

IdF

” time, (EdF=Sd)

the interval “IdF” is calculate through Smart Defrost algorithm (only when the compressor is ON).

3.4

 

CONTROL OF EVAPORATOR FANS

The fan control mode is selected by means of the “

FnC

” parameter:

FnC=C-n

  fans will switch ON and OFF with the compressor and

 not run

 during defrost

:

;

FnC= O-n

fans will run continuously, but not during defrost

After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd” parameter.

FnC=C-y

  fans will switch ON and OFF with the compressor and 

run

 during defrost;

FnC=O-y

  fans will run continuously also during defrost

An additional parameter “

FSt

” provides the setting of temperature, detected by the evaporator probe, above

which the fans are always OFF. This can be used to make sure circulation of air only if his temperature is lower
than set in “FSt”.

4.

 

KEYBOARD

To display and modify target set point; in programming mode it selects a parameter or confirm an
operation.
By holding it pressed for 3s when max or min temperature is displayed it will be erased.

To see the max. stored temperature; in programming mode it browses the parameter codes or
increases the displayed value. By holding it pressed for 3s the fast freezing  cycle is started.

To see the min stored temperature; in programming mode it browses the parameter codes or
decreases the displayed value.

By holding it pressed for 3s the defrost is started.

Switch ON and OFF the light of the cold-room

Switch ON and OFF the instrument.

KEY COMBINATIONS

 

To lock and unlock the keyboard.

 

To enter the programming mode.

 

To exit the programming mode.

4.1

 

USE OF LEDS

Each LED function is described in the following table.

LED

MODE

Function

ON

The compressor is running

FLASHING

- Programming Phase (flashing with LED 

)

- Anti-short cycle delay enabled

ON

The fan is running

FLASHING

Programming Phase (flashing with LED 

)

ON

The defrost is enabled

FLASHING

Drip time in progress

ON

The Fast Freezing cycle is enabled

ON

- ALARM signal
- In “Pr2” indicates that the parameter is also present in “Pr1”

ON

The light is on

4.2

 

HOW TO SEE THE MIN TEMPERATURE

1. 

Press and release the 

n

 key.

2. 

The “Lo” message will be displayed followed by the minimum temperature recorded.

3.

By pressing the 

n

 key or waiting for 5s the normal display will be restored.

4.3

 

HOW TO SEE THE MAX TEMPERATURE

1. 

Press and release the 

o

 key.

2. 

The “Hi” message will be displayed followed by the maximum  temperature recorded.

3.

By pressing the 

o

 key or waiting for 5s the normal display will be restored.

4.4

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED

To reset the stored temperature, when max or min temperature is displayed :
1.

 

Press SET key until “rST” label starts blinking.

N.B. After the installation RESET the temperature stored .

4.5

 

HOW TO SEE AND MODIFY THE SET POINT

1.

Push and immediately release the 

SET 

key: the display will show the Set point value;

2.

The SET LED start blinking;

3.

To change the Set value push the 

or 

n

 arrows within 10s.

4.

To memorise the new set point value push the 

SET

 key again or wait 10s.

4.6

 

TO START A MANUAL DEFROST

1.

Push the 

DEF 

key for more than 2 seconds and a manual defrost will start.

4.7

 

TO ENTER IN PARAMETERS LIST “PR1”

To enter the parameter list “Pr1” (user accessible parameters) operate as follows: