dIXEL
dIXEL
dIXEL
dIXEL
Operating Instructions
cod.
cod.
cod.
cod. 1592017410
1592017410
1592017410
1592017410
1592017410 XLH360 GB r1.0 15.04.2005.doc
XLH360
16/16
Label
Value
Menu
Description
Range
dot
20
Pr2
Delay of temperature alarm after closing the door
0 ÷ 250 min
AHc
Ab
Pr2
Humidity alarm configuration
rE = relative / Ab = absolute
AHL
0.0
Pr1
Low humidity alarm setting
0 ÷ 50 / Lci ÷ AHu
AHu
100
Pr1
High humidity alarm setting
0 ÷ 50 / AHL ÷ uci
AHH
2.0
Pr2
Humidity alarm recovery differential
0.5 ÷ 25
AHd
15
Pr2
Humidity alarm delay
0 ÷ 250 min
dHo
1.3
Pr2
Delay of humidity alarm at start-up
0.0 ÷ 23.5 h
doH
20
Pr2
Alarm delay at the end of defrost
0 ÷ 250 min
doA
20
Pr2
Open door alarm delay
0 ÷ 250 min ( 250 = nu )
tbA
oFF
Pr2
Relay status after pushing a key
on÷oFF
nPS
15
Pr2
Pressure switch number
0÷15
ot
0.0
Pr1
Thermostat probe calibration
-12.0 ÷ 12.0
oE
0.0
Pr2
Evaporator probe calibration
-12.0 ÷ 12.0
o3
0.0
Pr1
Humidity probe calibration
-10 ÷ 10
P2P
YES
Pr2
Evaporator probe presence
no
= absent /
YES
= present
P3P
YES
Pr2
Humidity probe presence
no
= absent /
YES
= present
Lci
0.0
Pr2
Readout with 4 mA
-999 ÷ 999
uci
100
Pr2
Readout with 20 mA
-999 ÷ 999
i1P
cL
Pr2
Configurable digital input polarity
cL =open / oP = close
i2P
cL
Pr2
Door switch digital input polarity
cL =open / oP = close
i1F
dor
Pr2
Digital input configuration
dor / PAL / EAL / bAL / Ht
odc
FAn
Pr2
Outputs status when open door
on / Fan / oFF
rrd
YES
Pr2
Outputs restarting after doA alarm
no = no / YES = yes
did
0
Pr2
Digital input alarm delay
0÷255 min.
oA1
LiG
Pr2
Light relay configuration 1
ALr
= alarm;
dEH
= dehumidifier;
onF
=
on/off;
Lig
= light,
ESt, dEF not select
oA2
ESt
Pr2
Light relay configuration 2
ALr
= alarm;
dEH
= not use;
onF
= on/off;
Lig
= light,
ESt= extractor, dEF =defrost
Adt
1
Pr2
Serial address for temperature
0÷247 num
AdH
1
Pr2
Serial address for humidity
0÷247 num
Ptb
- - -
Pr2
Parameter table
- - -
rEL
- - -
Pr2
Software release
- - -
Prd
- - -
Pr2
Probes display
Pb1÷Pb3
Pr2
- - -
Pr1
Access to the protected parameter list
- - -