9.DIP SWITCH SETTING
9-2. 485 TERMINATION
The 1
st
of DIP SW2 is used for 100W termination.
Set ON DIP SW2 -1
st
of only the last looped camera from the controller.
Even in case of only one camera, set ON DIP SW2 -1
st
of the camera.
9-3. PROTOCOL
The 3
rd
, 4
th
of DIP SW2 above are used for Protocol Setting.
Factory default: Pelco-D or Pelco-P (Auto detection)
DIP SW 2-3
rd
4
th
Protocol
OFF/OFF
Pelco-D or Pelco-P
ON/ON Not
used
ON/OFF Maxpro
9-4. BAUD RATE SETTING
The
7
th
, 8
th
SW of DIP SW2 above are used for BAUD RATE setting.
DIP SW can be configured as 4800bps, 9600bps.
Factory default : 2400bps.
*
PELCO
D
2400bps
* PELCO P 4800bps
*
MAXPRO
9600bps
DIP SW 2-7
th
DIP SW 2-8
th
BAUD
RATE
OFF OFF
Not
Used
OFF ON
2400bps
ON OFF
4800bps
ON ON
9600bps
* The 2
nd
, 4
th
, 5
th
, 6
th
of DIP SW2 are not used.
TERMINATION
SW1-ON
CAM 1
CAM 2
CAM n-1
CAM n