background image

1.0  DESCRIPTION

This 4-20mA isolator can be configured to accept most of the common
voltage found in both commercial and industrial applications. The input is
fully isolated from the output circuit. The isolator range can be specified at
the time of order, but if required the user may re-range the transmitter to
ta new range. The isolator is housed inside a plastic enclosure, suitable
for DIN rail mounting. Screw terminals are providedfor wire connections.
The enclosure provides side entry access to coarse offset and span
adjusters and a range selector switch.

2.0  SPECIFICATIONS @ 20ºC

2.1   OUTPUT

TYPE

Passive 2 wire current output

RANGE

4 to 20mA (30mA MAX.)

PROTECTION

Reverse connection plus overvoltage

VOLTAGE

10-30V DC

STABILITY

Typical 100ppm/ºC

RIPPLE

Less than 40

µ

A/V (Measured at 1V ripple 50Hz)

RESPONSE

200mS to reach 70% of final value

2.2  INPUT

TYPE

Isolated DC voltage covered by six ranges;

Range

Span

Offset

0

20   to 200mV

-20   to 80mV

1

0.2  to 1.0V

-0.1  to 0.4V

2

1.0  to 5.0V

-0.5  to 2.0V

4

5.0  to 25V 

-2.5  to 10V

8

25  to 48V

-5     to 25V

F

20  to 100V

-10   to 40V

The above settings are capable of covering most

standard industrial ranges. Range F is provided to
allow for –10 to +10V inputs. Note VMAX IN is limited
to 48V DC for BSEN 61010-1 compliance.

ISOLATION

500V AC (Flash tested to 1kV DC)

IMPEDANCE

>1M

ACCURACY

Typical linearity 

±

0.01% (0.05% maximum)

RANGE SELECT Coarse Settings, by side entry 16 setting position

rotary screw adjustement switches. Fine by front
access potentiometers. Range setting by side entry
rotary switch.

2.3   GENERAL

AMBIENT

0-50ºC ; 10-95% RH non-condensing

CONNECTION

Captive clamp screws

CABLE SIZE

4mm

2

 solid / 2.5mm

2

 stranded

3.0  INSTALLATION

IMPORTANT NOTE ¡

This isolator is not suitable for providing isolation from hazardous
voltages, such as mains supplies. It is intended for use in with low
voltage signals only.

3.1  MECHANICAL

This unit must be housed within a suitable enclosure that will provide
protection from the external environment, ensuring that the stated
temperature and humidity operating ranges are not exceeded. It is good
practice to mount the unit away from sources of electrical noise, such as
swichgear and transformers. The unit enclosure is designed to snap fit
onto a standard “TOP HAT” DIN rail. To remove from rail, apply pressure
at the bottom face at the back upwards the rail to release the spring clip
and tip away from the top. The unit may be mounted in any orientation
and stacked side by side along the rail. Span and offset fine adjustements
can be made from the front panel, whilst re-ranging the transmitter,
access to adjusters in the case side is requiered.

3.2  ELECTRICAL

Connections to the isolator are made via screw terminals. Wire protector
plates are provided inside each terminal. To maintain CE compliance
twisted pair (screened) cables are recommended. The correct type of wire
must be used for thermocouple inputs, mV inputs must use screened
copper wires, Incorrect sensor connection or sensor wire burnout will
result in the output current saturating up scale on standard units(optionally
downscale if requested at the time of the order).

It is good practice  to ensure all 4-20mA signal loops are grounded at one
point. Care must be taken when designing a 4-20mA circuit to ensure that
the total burden of the loop, (that is the total voltage requirements of all
the equipment connected in the loop at 20mA) does not exceed the loop
power supply voltage.

To operate correctly the isolator requires a minimum of 10V across its
output terminals.

The isolator is protected agains reverse connection and over voltage
Figure shows a typical 4-20mA circuit, the load resistor represents
equipment such as indicators, loggers, PLC etc.

KOS1015

  DIN RAIL

ISOLATED

TRANSMITTER

kos1015manualB.doc

30727040

Sep.99

KOSMOS      SERIES

WARRANTY

                                          

  The instruments are warranted against defective materials and
workmanship for a period of three years from date of delivery.

If a product appears to have a defect or fails during the normal use
within the warranty period, please contact the distributor from which
you purchased the product.

This warranty does not apply to defects resulting from action of the
buyer such as mishandling or improper interfacing.

The liability under this warranty shall extend only to the repair of the
instrument. No responsability is assumed by the manufacturer for
any damage which may result from its use.

Reviews: