DITEK Technical Support 

1-888-472-6100  www.diteksurgeprotection.com

 

 

 

 

 

 

        

DITEK Corporation

ONE DITEK CENTER

1720 Starkey Road

Largo, FL 33771

This Surge Protective Device (SPD) is a high performance device, designed to provide protection

for sensitive electronic loads connected to service panels, fire panels, or where the SPD is 

directly connected to the electronic device. Maximum protection will only be achieved if the SPD

is properly installed. Please read and follow the installation instructions carefully. 

NOTICE:

 This SPD should be installed by a licensed contractor in accordance with the National

and Local Electrical Codes and the following instructions.

APPLICATION

Wall mount, or desk top, surge suppression for shielded Ethernet, PoE and PoE extender circuits with field 

replaceable surge modules (DTK-NETMS, DTK-EXTMS).

              

              

  

    

     

INSTRUCTIONS

Note: This device is intended to be installed indoors on the wall or desk top closest to the point of use.

1. Test circuit prior to install to verify correct operation.

2. Turn off the power to the equiment to be protected.

3. This device can be mounted flush to a wall or placed on a desk top using best practice for securing.

4. Connect to equipment ground using the ground lug provided on side of enclosure. Use a minimum

    #14 AWG wire.

    Make sure the ground wire is as short as possible.

    

Ground Resistance Rule:

 Max ground resistance is 25 Ohms, 5 Ohms or less is optimum.

    This cannot be an assumed value and must be measured to assure proper grounding.

5. Plug the RJ45 tipped cable from the field or supply wiring to the 

“IN” 

UNPROTECTED

    RJ45 jack.

6. Plug a 3’ RJ45 male to RJ45 male patch cable from the 

“OUT” 

PROTECTED

 

RJ45 jack to the

    equipment to be protected. The 3’ patch cable will give this device time to react.

7. After all connections have been made and no hazards exist, restore power to the equipment.

Surge Module Install/Replacement:

 

There is no need to remove this protector from the wall, the 

surge modules can be installed/replaced while it is mounted. 

This product is made up of 4 individual surge modules for DTK-WM4 Series and 8 individual surge 

modules for DTK-WM8 Series. 

If 1 or more channels self sacrifice, or go end of life, you can replace that module as follows: 

1. Power down the individual circuit before servicing this device.

2. Insert a 3/8“ wide flat blade screwdriver into the top notch of the module’s bezel.

3. Gently turn the screwdriver to the right to loosen the bezel.

4. Insert the screwdriver into the bottom notch and again gently turn the screwdriver to the right until the

    module is free of the mating connector located at the rear of the wall mount chassis.

5. Remove module.

6. Insert new surge module into openening aligning the surge module with the integrated card guides.

    The orientation should match the revious module.

7. Press the new surge module in place making sure it is seated completely and the bezel is flush with the

    wall mount chassis.

8. Connect the RJ45 cables as mentioned in #5 and #6 of the 

INSTRUCTIONS

 listed above.

9. After all connections have been made and no hazards exist, restore power to the circuit.

Please see the illustrations page for more details.

 

 

Doc # INT-100178-001

Part No. 191609 Rev. 2

Drawn By: B. Aycock 9-20-18

Created By: R. Mitchell 4-23-19 

       INSTALL INSTRUCTIONS

             DTK-WM4 Series, DTK-WM8 Series

Note: 

The grounding detail for field installed network surge protectors is not applicable when a shielded 

protector using STP (Shielded Twisted Pair), with properly tipped shielded RJ45 connectors, has been 

terminated at a properly mounted and grounded shielded rack mount surge protector. The shield is used 

to dissipate the excess overvoltage. For example, DTK-MRJPOES, shielded single channel protector, use 

DTK-WM4NETS, shielded wall mount 4-channel protector.