TECHNICAL SPECIFICATIONS
Model
JPX1000RM
JPX2000RM
Capacity (VA)
1000VA
1920VA
Capacity (Watts)
600W
1200W
Input
Input Voltage Range
82V~148V
Frequency
50/60Hz auto sensing
Output
On Battery Output Voltage
Pure Sine Wave at /-10%
On Battery Output
Frequency
50/60 Hz +/-1%
Overload Protection
Yes
AVR Function
Boost Function
Yes
Buck Function
Yes
Physical
Total # of UPS Receptacles
Nema 5-15R *8
Maximum Dimensions
(H x D x W)
88mm x 400mm x 433mm
Battery
Sealed Maintenance Free
Lead Acid Battery
24Vdc
Typical Recharge Time
8 Hours
Warning Diagnostics
Indicators
LCD
Communication
Communication port
USB,RS232
Environmental
Operating Temperature
32
F to 122
F ( 0
C to 40
C )
Operating Relative Humidity
0 to 90% NON-CONDENSING
Management
Auto-Charger
Yes
Auto-Restart
Yes
TROUBLE SHOOTING
Problem
Possible Causes
Remedy
Abnormal
Mains normal but not
works in AC mode
1. AC Input missing
1. Check AC input connection.
2. Input Breaker is tripped
2. Unplug the power cord of the UPS
then press the circuit breaker knob.
The UPS will not turn on.
The on/off Button is
designed to prevent damage
by rapidly turning it off and
on.
Turn the UPS off. Wait 10 seconds
and then turn the UPS on.
The unit is not connected to
an AC outlet.
The unit must be connected to a
100-127V 50/60Hz outlet.
The battery is worn out.
Contact technical support.
Mechanical problem.
Outlets do not provide
power to equipment
Circuit breaker is tripped due
to overload
Turn the UPS off and unplug at least
one piece connected equipment.
Unplug the power cord of the UPS then
press the circuit breaker knob.
Batteries are discharged
Allow the unit to recharge for at least 4
hours.
Unit has been damaged by a
surge or spike.
Contact technical support.
Alarm code A01
Site Fail:
Line and neutral conductors
of UPS Input are reversed or
the Ground is disconnected.
Check the input plug and socket.
Alarm code A06
Battery low:
Battery capacity is low, UPS
will turn off soon
1. Shut off non-essential equipment.
2. Save your data and turn off the
computer.
Alarm code A14
Overload:
Your equipment requires
more power than the UPS
can provide.
1. Shut off non-essential equipment.
Alarm code A18
Over Temperature
1. Shut off non-essential equipment.
2. Check the fan for operation and if
the ventilation hole has been covered.
Fault
Fault code F09
Output Short :
Output circuit short.
1. Shut down the UPS
2. Your attached equipment may have
problems, please remove them and
check again.
Fault code F14
Overload:
Your equipment requires
more power than the UPS
can provide.
It will shutdown.
Shut off non-essential equipment. If
this solves the overload problem, the
UPS will transfer to normal operation.
Fault code F18
Fan fail :
Fan has been damaged.
1.Shut down the UPS
2.Replace the fan
Fault code F19
Over Temperature
1. Shut down the UPS. Restart the
UPS to Check the fan for operation
and if the ventilation hole has been
covered
2. Contact technical support for repair.
SOFTWARE DOWNLOAD
Power Master management software provides a user-friendly interface for your power systems. The
graphic user-interface is intuitive and displays essential power information at a glance. Please follow
procedure below to install the software.
Installation procedure: