WIH 120TU
English
12 Device information
1
Type and order code
WIH 120TU
2
Design
Heat source
Water
2.1
Model
Universal
2.2
Controller
integrated
2.3
Thermal energy meter
Integrated
2.4
Installation location
Indoors
2.5
Performance levels
2
3
Operating limits
3.1
Heating water flow
°C
20 to 70 ±2
3.2
cold water (heat source)
°C
+7 to +25
4
Flow / sound
4.1
Heating water flow / free compression (max)
Nominal flow in accordance with EN 14511
at W10...7 / W35...30
m³/h / Pa
21.2 / 36500
at W10...7 / W45...40
m³/h / Pa
20.8 / 38400
at W10...7 / W55...47
m³/h / Pa
12.6 / 78900
at W10...7 / W65...55
m³/h / Pa
9.9 / 92300
Minimum heating water flow
m³/h / Pa
9.9 / 92300
4.2
Cold water flow rate / internal pressure differential
Nominal flow in accordance with EN 14511
at W10...7 / W35...30
m³/h / Pa
28.1 / 30820
at W10...7 / W45...40
m³/h / Pa
26.6 / 28000
at W10...7 / W55...47
m³/h / Pa
24.1 / 23150
at W10...7 / W65...55
m³/h / Pa
21.7 / 19230
Minimum cold water flow rate
m³/h / Pa
21.7 / 19230
4.3
Sound power level according to EN 12102
dB(A)
70
4.4
Sound pressure level at a distance of 1m
1
dB(A)
55
5
Dimensions, weight and filling quantity
5.1
Device dimensions
2
H x W x L mm
1890 x 1350 x 775
5.2
Weight of the transportable unit(s) incl. packaging
kg
807
5.3
Device connections for heating
inches
Rp 2''
5.4
Device connections for heat source
Inches
Rp 3''
5.5
Refrigerant / total filling weight
type/kg
R134a / 24.5
5.6
GWP value / CO
2
equivalent
--- / t
1430 / 35
5.7
yes
5.8
Lubricant / total filling quantity
type/litres
Polyolester (POE)/16.0
5.9
Volume of heating water in device
Litres
22.9
5.10 Volume of heat transfer medium in device
Litres
23.8
6
Electrical connection
6.1
Supply voltage / fuse protection / RCD-Type
3~/PE 400 V (50 Hz) / C 100A / A
6.2
Control voltage / fuse protection / RCD-Type
1~/N/PE 230 V (50 Hz) / C 13A / A
6.3
Degree of protection according to EN 60 529
IP 21
6.4
Starting current with soft starter
A
120
6.5
Nominal power consumption W10/W35 / max. power consumption
3
kW
23.0 / 45.0
6.6
Nominal current W10/W35 / cos
A / ---
49.6 / 0.67
6.7
Max. power consumption of compressor protection
(per compressor)
W
130 / thermostatically controlled
6.8
Power consumption of pump(s)
kW
up to 0.52
Summary of Contents for WIH 120TU
Page 2: ......
Page 16: ...DE 14 452234 66 57 FD 9908 www gdts one Deutsch WIH 120TU ...
Page 42: ...FR 14 452234 66 57 FD 9908 www gdts one Français WIH 120TU ...
Page 58: ...A XVI 452234 66 57 FD 9908 www gdts one Anhang Appendix Annexes WIH 120TU ...
Page 59: ...www gdts one 452234 66 57 FD 9908 A XVII WIH 120TU Anhang Appendix Annexes ...