Electrical Installation
WARNING:
The installation of the electric fireplace must comply with the applicable Local and/or National
Electrical Codes and utility requirements.
CAUTION:
A dedicated, properly fused 15 Amp circuit is recommended, rated for 120 V. A dedicated circuit
will be required if, after installation, the circuit breaker trips or fuse blows on a regular basis when the heater is
operating. Additional appliances on the same circuit may exceed the current rating of the circuit breaker.
!
NOTE:
If required, the service cable can be secured through the electrical cover using a 1/2” (1.3 cm) approved
strain relief connector.
120 V Hardwire Installation (Figure 10)
WARNING:
Use the appropriate wire to meet local and national electrical codes for rated power consumption.
1. Connect the black L wire from the unit to the live wire from the power supply with a wire connector.
2. Connect the white N wire from the unit to the neutral wire from the power supply with a wire connector.
3. Connect the green G wire from the unit to the ground wire from the power supply with a wire connector or attach the
grounding wire to the cover with the provided grounding screw, by placing the wire between screw and lock washer
and tighten.
4. Ensure all wire connections are tight.
Installation
FIR
EP
LAC
E
JUNC
TI
O
N
B
O
X
120 V
POWER
SUPPLY
(BREAKER
PANEL)
WHITE - N
WHITE – N
BLACK – L
GROUND - G
BLACK – L1
FIR
EP
LAC
E
JUNC
TI
O
N
B
O
X
240 V
POWER
SUPPLY
(BREAKER
PANEL)
WHITE - N
RED – L2
RED – L2
WHITE – N
BLACK – L
GROUND - G
GROUND - G
BLACK – L1
GREEN – G
Figure 10
120V Installation - Wall Switch (Figure 11)
!
NOTE:
Use a single pole, single throw (On/Off) wall switch that is rated for a minimum of 15 amps.
WARNING:
Use the appropriate wire to meet local and national electrical codes for rated power consumption.
1. Connect the black L wire from the unit to the live wire from the main power through the wall switch, ensuring all live
connections are connected with a wire connector.
2. Connect the white N wire from the unit to the neutral wire from the power supply with a wire connector.
3. Connect the green G wire from the unit to the ground wire from the power supply with a wire connector or attach the
grounding wire to the cover with the provided grounding screw, by placing the wire between screw and lock washer
and tighten.
4. Ensure all wire connections are tight.
FIR
EP
LAC
E
JUNC
TI
O
N
B
O
X
120 V
POWER
SUPPLY
(BREAKER
PANEL)
WHITE - N
BLACK – L1
WHITE – N
BLACK – L
GROUND - G
WALL
SWITCH
GREEN – G
Figure 11