DGM INSTALLATION AND MAINTENANCE MANUAL
40
700135-0000 Rev. O
Send) value. These are the only two functions that can be accessed without having a
valid passnumber entered.
5.2 PANEL CONTROLS
The following is a list of the controls located on the front panel of the DGM. Numerical
buttons are for entering information such as time, zone numbers, and function numbers.
5.2.1 READ
Press the READ button after entering a zone number to display the status of the zone
number selected. If your entry is not available on the DGM panel, the display will read
“NOT VALID ENTRY.”
If the READ button is pressed when several zones are either in Alarm, Trouble, or Out of
Service, it will cause the next zone to be displayed. This will allow you to quickly advance
through the list.
The READ button is also used by some programming functions to view a specific zone, or
to advance through zones.
5.2.2 IN/OUT
After entering a zone number, press the IN/OUT button to toggle the selected zone in or
out of service. The display will show the current status of the zone, and the panel will
transmit the information to the SYSTEM 3505 PRISM LX. You must have the IN & OUT
OF SERVICE option installed on your DGM panel. Otherwise, it will respond by
displaying "??????" on the lower line of the display. The operator at the SYSTEM 3505
PRISM LX also has the ability to place zones on the DGM panels in and out of service.
When a zone is out of service, future alarm and trouble conditions on that zone will not be
reported to the SYSTEM 3505 PRISM LX until the zone is restored to service.
The IN/OUT button is also used by some programming functions as a shortcut to setting a
parameter on all zones at one time. For example, by using IN/OUT with Function 22 you
are able to set all zones in the panel to Normally Closed or Normally Open at the same
time.
5.2.3 CLR/SIL
Press the CLR/SIL button to clear any number entered via the numeric keypad, or to
silence the beeper. Upon initialization, push this button to clear the display, and show the
time and alarm mode.
As a shortcut, press CLR/SIL twice to display the current RTS value without entering the
Request to Send Function (11).
The CLR/SIL button is also used by programming functions to clear the display.
5.2.4 ENTER
After entering the password, press ENTER to allow access to the programming mode.
Once in programming mode, press ENTER to have the DGM program accept information
entered from the keypad.