function is five seconds. The default may be changed to any amount from one to
255 seconds.
To view or change Function 26, press “26”, then FUNC or, if you are viewing the
previous function, just press FUNC. The second line of the display will read “26 - AC
Delay = 016.” A message will scroll on the first line:
The AC Power Fail Delay timing is 016 seconds long. To change the
AC Power Fail Delay timing, enter the new value, then press ENTER.
The AC Power Fail Delay value can be from 1 to 255. The default
value is 5 seconds. Press CLR/Sil to clear display or FUNC to view
next function.
Press CLR/SIL to clear the display. Press FUNC to advance to the next function.
4.3.28 FUNCTION 27 (PIN LENGTH)
This function sets the PIN NUMBER length. The choices are either four or six digits.
The default is four digits. The pins can be 0000 through 9999. When four digits are
used, up to 250 different pins may be stored. When six digits are used, up to 160
different pins may be stored. This option is only valid if Function 28 is used.
CAUTION
: Changing this function will cause any stored PINS to be erased.
To view or change Function 27, press “27”, then FUNC or, if you are viewing the
previous function, just press FUNC. The second line of the display
will read “27 - Pin
Length.” A message will scroll on the first line:
Pin Number length is 4. Press the TGGL button to change. Press
CLR/SIL to clear display or FUNC to view next Function.
Press CLR/SIL to clear the display. Press FUNC to advance to the next function.
4.3.29 FUNCTION 28 (ACTIVATE KEYPAD)
This function allows the use of a DIGITIZE, INC. Keypad Part No. 400492-0001.
After installing the keypad, select the address of the keypad and the zone to which it
will be assigned. Keypad values are from 0-15. The keypad can be assigned to any
zone. Initially, the keypad will assign a 30 second entry/exit delay to the zone. If the
entry/exit delay needs to be changed to a higher value (more delay) or disabled
(less delay), you must go back to Function 12 and change the zone delay for the
zone assigned to the keypad.
To view or chan
ge Function 28, press “28”, then FUNC or, if you are viewing the
previous function, just press FUNC.
The second line of the display will read “28 -
Timed Zones.” A message will scroll on the first line:
Activate keypad by assigning a zone to it. Use the READ button to
select the keypad to update. Enter the desired Timed Access Zone
(1-64), then press the ENTER button. To disable the keypad, press
ENTER without entering a zone number. Press CLR/SIL to clear
display or FUNC to view next Function.
Press CLR/SIL to clear the display or FUNC to advance to the next function.
Summary of Contents for DGM-32/64
Page 4: ......
Page 6: ......
Page 10: ......
Page 18: ...DGM INSTALLATION AND MAINTENANCE MANUAL 8 700135 0000 Rev O...
Page 56: ...DGM INSTALLATION AND MAINTENANCE MANUAL 46 700135 0000 Rev O...