DGM INSTALLATION AND MAINTENANCE MANUAL
700135-0000 Rev. O
15
2.11.2 WIRING
Field wiring for this board must be tested and connected prior to assembling the rest
of the unit. Connect the communications line(s) to the proper terminals. Transmit
(TX) must be connected to Receive (RX). Be sure to keep protective caps on any
used terminals.
2.11.2.1 Terminals 1 and 2 (Channel A)
These terminals are used for multiplex communications in a system utilizing the
Fiber Optic interface Style 3 or Style 7 wiring.
2.11.2.2 Terminals 3 and 4 (Channel B)
These terminals are connected to the secondary channel of a system utilizing the
Fiber Optic interface Style 3 or Style 7 wiring.
2.11.2.3 P1
This connector must be plugged into P1 of the main board of the DGM. This
connector is polarized for proper installation.
2.12 EXP-8Z
2.12.1 GENERAL
Each EXP-8Z EOL interface board may be jumper selected for any available zone
group for both the DGM-32 and DGM-64. This board is optional and is only used
when the DGM is connected within 20 feet of the initiating device. Use of these
boards and configuration of the DGM is a special order. These boards are available
primarily to customers who wish to expand existing DGM panels that already contain
EXP-8Z EOL cards. The current DGM design uses one or two 32 Zone EOL cards in
lieu of the EXP-8Z cards.
The EXP-8Z board does not provide lightning protection for each zone input. Please
refer to
Section 2.13.1, 32 Zone EOL.
2.12.2 INSTALLATION
STEP 1: Place an EXP-8Z board over the mounting holes and start the top left and
top right mounting screws.
STEP 2: Start the lower left and lower right screws and tighten all mounting screws.
STEP 3: Connect the ribbon cable plug from P0 of the main board or from P1 of the
previous EXP-8Z to P1 of the EXP-8Z being installed.
2.12.3 WIRING
2.12.3.1 BS1 and BS2
Barrier strips BS1 and BS2 contain terminals for the connection of field wiring to the
Class B zone initiating inputs. Zone numbering is shown for the EXP-8Z supplied
with the system. For additional boards, terminal designations increase by eight for
each expansion board.
Summary of Contents for DGM-32/64
Page 4: ......
Page 6: ......
Page 10: ......
Page 18: ...DGM INSTALLATION AND MAINTENANCE MANUAL 8 700135 0000 Rev O...
Page 56: ...DGM INSTALLATION AND MAINTENANCE MANUAL 46 700135 0000 Rev O...