2
sion heartbeat rate shall be set as
90
seconds (panel Section [851] [004] = 005A/90). The supervision win-
dow at the Signal Receiver Centre (SRC)'s receiver shall be programmed as maximum 00B4/180 seconds.
• For UL Residential fire and burglary applications the GS2060/GS2065/TL260GS/TL265GS can be used as
primary communication channel via either GSM or Ethernet, or as a back-up in conjunction with the DACT
(30 day test transmission is required on each channel).
• For UL Commercial Burglary applications the TL260GS/TL265GS module can be used as Dual Signalling
Line communication system (GSM and Ethernet channels used in redundant configuration), Standard Line
Security and as Encrypted Line Security.
• The supervision heartbeat shall be enabled (panel Section [851] [005] Toggle Option [1] (Ethernet) and/or
Toggle Option [2] (GSM) shall be ON), Toggle Option [3] (Supervision Type) shall be ON and the supervision
heartbeat rate shall be selected as 0087/135 seconds Option [004] = 0087. The supervision window at the
supervising station shall be maximum 00C8/200 seconds. For Encrypted Line Security systems the encryp-
tion AES128 bit shall be enabled at the monitoring station receiver.
• For UL Commercial Burglary installations, the GS2060/ GS2065 are listed as a primary (sole) communica-
tion means (heartbeat must be enabled) or for supplementary (back-up) use in conjunction with a Plain Old
Telephone Service (POTS) line (dialer). When the heartbeat transmission over the Ethernet or GPRS/GSM
network is enabled, using the TL260GS/TL265GS with a compatible control unit listed for standard/
encrypted line security, it can provide line security for the alarm system over the primary line.
•
The TL260GS and TL265GS are also suitable to be used with a compatible control unit listed for dual line secu-
rity transmission when used in conjunction with a Digital Alarm Communicator Transmitter (DACT) or a Public
Switched Data Network (PSDN) transmitter, where the PSDN provides the line security and is the primary line.
In this mode, alarm signals are required to be sent simultaneously over both communication methods.
Ratings
Compatibility
Products or components of products, which perform communications functions only shall comply with the
requirements applicable to communications equipment as specified in UL60950 or CAN/CSA-C22.2 No. 950-1,
Information Technology Equipment - Safety - Part 1: General Requirements. Where network interfaces are
internal to the control unit or receiver, compliance to CAN/CSA-C22.2 No. 950-1 is adequate. Such components
include, but are not limited to: hubs; routers; NIDs; Third party communications service providers; DSL
modems; and Cable modems.
Table 1: Communicator Ratings
MODEL
GS2060
GPRS/GSM ONLY
TL260GS
ETHERNET & GPRS
GS2065
GPRS/GSM
ONLY
TL265GS
ETHERNET &
GPRS
POWER SUPPLY RATINGS
Input Voltage
11.1~12.6V DC: The panel Bell output
shall be derated:
700mA- (Communicator mA) = (derated
Bell output).
11.1 ~ 12.6V DC
(From PC-Link Header)
CURRENT CONSUMPTION
Standby Current
65mA @ 12V
100mA @ 12V
65mA @ 12V
100mA @ 12V
Alarm (Transmitting) Current
400mA @ 12V during transmission
Operating Frequency
Quad band 850MHz, 900MHz, 1800MHz, 1900MHz
Typical Antenna Gain
2db
i
ENVIRONMENTAL SPECIFICATIONS
Operating Temperature
0°C - 49°C (32°F- 120°F)
Humidity
5% ~ 93% relative humidity, non-condensing
MECHANICAL SPECIFICATIONS
Board Dimensions (mm)
100 × 150 × 15
100 × 150 × 18
100 × 150 × 15 100 × 150 × 18
Weight (grams)
310 (with mounting
bracket)
320 (with mounting
bracket)
68
78
Table 2: Compatible Receivers, Control Panels, and Cabinets
COMMUNICATOR
RECEIVER/
PANEL
DESCRIPTION
GS2060/TL260GS
GS2065/TL265GS
Receiver
• Sur-Gard System I Receiver, version 1.1+
• Sur-Gard System II Receiver, version 2.0+
• Sur-Gard SG-DRL3-IP, version 2.2+(for Sur-Gard System III Receiver)
GS2060/TL260GS
Control Panel
and Cabinets
• Power Series PC1864, version 4.1+
• Power Series PC1832, version 4.1+
• Power Series PC1616, version 4.1+
• Cabinets
:
PC5003C/PC4050C
GS2065/TL265GS
Control Panel
• PC9155 version 1.1+