Digital Lumens Network Gateway 3 Installation Instructions Download Page 1

Network Gateway 3

 

Installation Instructions

Installation Procedure

The Network Gateway 3 creates a network bridge between the Ethernet components in the lighting network infrastructure 

and the wireless light fixtures. Each gateway manages communication for up to 50 fixtures within RF range. The Gateway 

is a PoE (Power over Ethernet) device that eliminates the need for power service installation. An optional external  

low-temperature AC-DC power supply is available, if PoE functionality is not desired. 

Installation Guidelines

•  For guidance regarding the preferred locations for Gateways within the facility, consult with Digital Lumens 

prior to installation.

•  As a general strategy, install Gateways toward the center of each room or designated wireless zone.
•  Position Gateways at the approximate height of the fixtures, with a minimally obstructed line-of-sight to  

those fixtures.

•  Install Gateways in low-collision-risk areas, where forklifts and other machinery will not come in contact  

with the Gateway housings.

•  Install Gateways in areas free from condensation.

This product must be installed by a qualified electrician 

in accordance with national, state, and local electrical 

and construction codes.

To avoid risk of electrical shock, disconnect power 

before installing or wiring Network Gateway 3. 

Network Gateway 3 has no user-serviceable parts.  

Do not open enclosure.

Do not use Network Gateway 3 if the enclosure, power 

connector, or optional power supply is damaged.

Do not apply paint, lubricants or other coatings to 

Network Gateway 3 or fasteners.

Do not attempt to install Network Gateway 3 until you 

read and understand the specifications and all product 

safety information.

!

!

!

Product Safety

Figure A

Figure B

Step 1: Install the Gateway Housing

1. Option A:

 

Using two toggle bolts, truss clamps, or other hardware 

(not included), mount the Gateway housing on a truss or suitable 

ceiling structure (see Figure A). The mounting holes have a .25 in  

(6.4 mm) diameter and are spaced 6.0 in (15.2 cm) apart.

Hint:

 

For better wireless connectivity, mount the Gateway housing  

on the lower portion of the truss or ceiling structure.

Option B:

 

Using two screws or other hardware (not included), 

mount the Gateway housing on a suitable surface (see Figure B).  

The mounting holes have a .25 in (6.4 mm) diameter and are  

spaced 6.0 in (15.2 cm) apart.

2. Record the serial number and location of the Gateway in a lighting 

diagram depicting the facility or serial number sticker book. If you 

have a barcode scanner, you can scan the barcode label on the 

device label to rapidly record the serial number. 