EVO Control Panel
5
Figure 4: Sample Power Requirement Calculations
Do not use the same transformer for the control panel and the external power
supplies. Do not install modules more than 914m (3000ft) from the control panel.
2.12 Keypad Zone Connections
Every keypad, except Grafica, has one hardwire input terminal.
Even with the ATZ feature enabled in the control panel, only one device can be
connected to the keypad’s hardwired input terminal. Tamper is not recognized on
keypad zones. The keypad zone follows the control panel’s EOL definition.
The keypad communicates the status of the zone to the control panel via
the combus. The detection device is connected as shown in
Figure 5: External Power Supply Connections
2.13 Addressable Zone Connections
The control panel includes eight hardwired input terminals for use with
traditional hardwired (non-combus) door contacts, smoke detectors and/or
motion detectors.
The control panel also supports hardwire zone expansion modules.
shows single zone (ATZ disabled) hardwire input terminal connections
recognized by the Digiplex EVO system. For UL listed installations, use
EOL resistor part #2011002000.
Power required by devices connected to control panel’s
auxiliary output must not exceed the auxiliary output’s limit:
(A) + (B) + (C) + (D) + (E) + (F) + (G) = 368mA<700mA = OK
Control Panel
aux. output
= 700mA
61m (200ft)
15m (50ft)
APR-PRT3
(A) = 25mA
EVO641
(D) = 110mA
7.5m (25ft
)
15m (50ft)
DGP2-70
(E) = 30mA
7.5m (25ft)
APR-ZX8
(B) = 30mA
30m (100ft)
22 AWG
EVO641
(F) = 110mA
15m (50ft)
EVO641
(G) = 110mA
91m (300ft)
290m (950ft)
DGP2-60
(C) = 30mA
305m (1000ft)
As indicated in
page 4, this run of wire can
support 700mA. Total mA on
this run of wire:
(A) 25mA + (B) 30mA =
55mA<700mA = OK
As indicated in
page 4, this run of wire
can support 454mA. Total
mA on this run of wire:
(D) 110mA + (E) 30mA +
(F) 110mA + (G) 110mA
= 360mA<454mA = OK
As indicated in
page 4, this run of wire
can support 136mA. Total
mA on this run of wire:
(A) 25mA + (C) 30mA =
55mA<136mA = OK
Module
Module
Power Supply
152m (500ft) from control panel
152 (500ft) from control panel’s aux. output
Therefore this run = max. 273mA
610m (2000ft) from control panel
152m (500ft) from power supply
Therefore this run = max. 273mA
Milliamps required by devices connected
to a power supply do not draw power
from the control panel’s auxiliary output.