SC-Xnet
Description
Enable
Enable
Activate wireless Xnet.
This option requires a special hardware module connected to X2 RS485.
Disable
Disable wireless Xnet.
Discover
Find other Xnet devices within range.
Connect
Allow access to other Xnet devices.
X-Lock
Wireless Air lock for up to 5 controllers.
Clear all
Reset all Xnet settings to factory defaults.
Settings
Channel
Network ID
6. Setup: Placing into operation with encoder
6.1 GENERAL INFORMATION
Please note that the Quick Setup is aborted if the position counter is exceeded during setup.
Then use the encoder scale to reduce the number (see System Setup -> Position Sensor -> Scale).
Then select the Scale value = 2. The count value is now halved.
To check whether the positions are within the number range of the controller (-32000 - +32000),
use System diagnostic -> Position and move the door to fully open and fully closed position in
“Dead-man“ with the membrane keys. Then check whether the value is within the range.
Note: At the start of the teach-in travel, the door/gate should be in the half-open position. If the
operator moves against a mechanical stop in the open or closed position during the check of
the direction of movement, error messages with abort of the learning travel are possible.