
DSP-15 User Manual
Page 10 of 23
DSP15_MAN_C
Output B Selection (DIP Switches 5 and 6)
Output B can be programmed to operate in one of four different modes that are selected using DIP switches 5
and 6. The following table identifies these four modes:
DIP Switch
Output B Mode
of Operation
5
6
OFF
OFF
True Presence
OFF
ON
Pulse on Entry
ON
OFF
Pulse on Exit
ON
ON
Fail
True Presence:
The B output will be energized whenever a vehicle is present over the loop detection area. The
A output can be modified by the delay and/or extension timing settings. The B output will not use these timing
settings. For example, if 2 seconds of delay is set, output B will energize as soon as the vehicle is detected, while
output A will wait for two seconds of continuous presence prior to energizing.
Pulse on Entry:
Every time the loop is occupied, a single 250 milliseconds pulse will be output on the B output.
Pulse on Exit:
Every time the loop becomes vacant or a vehicle is tuned out, a single 250 milliseconds pulse will
be output on the B output.
Fail:
If the DSP-15 recognizes some type of loop failure, a continuous output on the B output will be given. The B
output will remain activated until the failure is corrected.
The following figures show the effects of delay and extension on the A & B outputs. The numbers between
edges are the number of seconds in that period.
Figure 2: Outputs with No Delay or Extension