- 10 -
Batt Temp
Sensor
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
CN1:
TEMP (1,2): battery temperature sensor for lead
acid battery.
CT-L1 (3,4): current transformer (CT1) for“zero
export to CT”mode clamps on L1 when
in three phase system.
CT-L2 (5,6): current transformer (CT2) for“zero
export to CT”mode clamps on L2 when
in three phase system.
CT-L3 (7,8): current transformer (CT3) for“zero export to CT”mode clamps on L3 when in
three phase system.
CN2:
G-start (1,2): dry contact signal for startup the
diesel generator.
When the "GEN signal" is active, the open contact
(GS) will switch on (no voltage output).
G-valve (3,4): reserved.
Grid_Ry (5,6):
RSD (7,8): When battery is connected and the
inverter is in "ON" status, it will provide 12Vdc.
Parallel A: Parallel communication
port 1 (CAN interface).
Parallel B: Parallel communication
port 2 (CAN interface).
Meter_485: for energy meter
communication.
ModeBUS: Reserved.
BMS: BMS port for battery
communication(CAN/RS485).
DRM port:Logic interface for
AS/NZS 4777.2:2020
CT -L1
CT -L2
CT -L3
Gen start-up
N/O Relay
Parallel_A
CN1:
TEMP: 1,2
CT_1: 3,4
CT_2: 5,6
CT_3: 7,8
Parallel_B Meter-485
ModeBUS BMS
GS (diesel generator startup signal)
relay
coil
open
contact
G
S
3.3.2 Function port definition
CN2
: G_start: 1,2
G_valve: 3,4
Grid_Ry: 5,6
RSD: 7+, 8-
CN1
CN2
Inverter
DRM port