The reac�ve power regula�on func�on is disabled. The PF is fixed at +1.000
"OFF" Mode
Adjust reac�ve power output in %.
Q(%)
The power factor (PF) is fixed and the reac�ve power is regulated by the parameter
PF. The PF ranges from 0.8 leading to 0.8 lagging.
•Leading: the inverter is sourcing reac�ve power to the grid.
•Lagging: the inverter is injec�ng reac�ve power into the grid.
"PF" Mode
The inverter provides a reactive power regulation function.
Tap
Reactive Power Regulation Mode
to select proper regulation mode and set the
corresponding parameters.
ActiveP 0%
Q-Mode OFF <<
ActiveP 0%
Q-Mode Q(P) <<
ActiveP 0%
Q-Mode PF<<
ActiveP 0%
Q-Mode Q(%)<<
ActiveP 0%
Q-Mode PF(P) <<
ActiveP 0%
Q-Mode Q(U) <<
RecGra 0.00% <<
Frec 50.10Hz
RecDly 0.00
OK << Cancel
When the frequency exceeds
Fstop
: 51.5Hz, the inverter output should stop (ie 0 W).
When the frequency is lower than
Fstop
: 51.5 Hz, the inverter will linearly increase the power
output with a gradient of 100% Pmax/Hz un�l it reaches
Fstr
: 50.5 Hz.
In the hysteresis mode, when the frequency is lower than
Fstop
: 51.5 Hz, the inverter will not
increase the power output un�l it is lower than RecPT: 50.1 Hz.