background image

59651 

Issue 1 

Date: January 2014                  

www.dextralighting.co.uk

 

Page 1 of 2                              

 

                                                                                                                                             

29 

203.7 

2

2

.5

 

2

6

.2

 

INSTALLATION INSTRUCTIONS 

LED3RO/NM3

 

 

Refer to 

www.dextralighting.co.uk

  for specific data 

 

Description 

An  LED  driver  and  battery  pack  in  an  articulated  plastic 
housing,  connected  via  a  500mm  wiring  loom  to  the 
lamphead  assembly,  which  contains  the  high  power  white 
LED and indicator LED for emergency use only.    
 
The LED control gear has reinforced insulation between the 
supply  and  the  battery  circuit,  and  a  battery  charger  with 
short circuit protection that will continue to operate when the 
short is removed. 

 
Luminaire Dimensions (mm) 
 

 

 
 
 
 
 
 
 
 
 
Specification 

Supply Voltage 

 

230Vac ± 10% 50/60 Hz 

Supply Current 

 

30mA max 

Ambient Temperature  

0°C to +35°C 

Max Case Temp (Tc) 

70°C 

Conductor Size   

0.5 

– 1.5mm

2

 

Mounting Screws  

M4 

Weight of Control Gear 

240g (incl. battery) 

Weight of Lamphead 

80g 

Photometric Data  

Refer to www.dextralighting.co.uk 

IP Rating of Luminaire 

IP30 

 

Batteries 

The  luminaire  includes  a  2.2Ah  3.6V  rechargeable  NiMH 
battery  pack  for  3  hour  operation.  When  the  luminaire  no 
longer  meets  3  hours  duration  replace  the  batteries, 
observing  the  battery  polarity,  as 

permanent  damage  to 

the control gear will occur if they are reversed.

  

 

Relevant Standards

 

EN 61347-2-7 

 

 Lamp control gear 

EN 61347-2-13   

 LED control gear 

EN 60598-2-22   

 Luminaire  

 
Warranty

 

This product is guaranteed for three years and covers faulty 
workmanship  and  materials.  The  guarantee  on  the  NiMH 
batteries  is  one  year.  This  “Return  to  Base”  warranty 
requires  that  the  product  is  used  within  the  terms  and 
conditions stated above, in our literature and on our website. 
Products  returned  to  us  under  warranty  must  be  carriage 
paid.    Dextra  Lighting  Ltd.  accept  no  liability  for  costs 
incurred. 
 

IMPORTANT 

Please ensure that the information contained in this leaflet is 
passed on to the user/maintenance engineer. 
 
 
 
 
 
 

 
 

 
Electrical Installation 

The luminaire must be installed by 
a  qualified  person  in  accordance 
with  the  current  building  and 
wiring regulations. 
Luminaires  comply  with  the  EMC 
directive 

in 

both 

modes 

of 

operation,  mains  and  emergency.  
The  black  battery  lead  should  be 
connected  only  at  the  time  of 
commissioning. Remove middle cover to attach battery lead 
(as  shown),  remove  end  cover,  to  attach  mains  supply. 

When  the  mains  supply  and  battery  leads  are 
connected,  both  white  covers  should  be  screwed  into 
place to protect from electric shock

 

The  LED  is  non-replaceable  and  the  supplier  should  be 
contacted in the unlikely event of a failure. 

 
IMPORTANT 

Mark  the  luminaire  with  the  date  of  commissioning  in  the 
space provided on the label. 
 

Operation

 

Upon connection of a permanent mains supply the indicator 
LED lights to show the battery is receiving charge. Following 
an initial charging period of 24 hours the unit will be capable 
of providing 3 hours emergency duration. 

 

414.66 

Driver 

Battery 

Reviews: